Form I-Y, P/N 273646R6, Page 51

Gas Pressure Safety

Switches, Option BP4

See Manifold illustrations,

FIGURE 23, page 39, or

FIGURE 24A, page 43.

The optional gas pressure switches are safety controls designed to protect the mani-

fold and burner from extreme upstream gas piping system failures that would cause an

increase or decrease in the regulated gas pressure.
The low gas pressure switch is an automatic reset which is set to activate if the gas

pressure is 50% of the minimum as stated on the rating plate.
The high gas pressure switch is a manually reset switch that is set to activate if the gas

pressure is 125% of the manifold pressure stated on the rating plate.

BTUH Inputs and Capacities by Altitude in Canada

Altitude

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Feet

Meters

H50

H75

H100

0-2000

0-610

50,000

40,000

N/A

10,000

75,000

60,000

N/A

15,000

100,000

80,000

50,000

20,000

2001-4500

611-1373

45,000

36,000

N/A

9,000

67,500

54,000

N/A

13,500

90,000

72,000

45,000

18,000

Feet

Meters

H200

H300

H400

0-2000

0-610

200,000

160,000

100,000

40,000

300,000

240,000

150,000

60,000

400,000 320,000

200,000

80,000

2001-4500

611-1373

180,000

144,000

90,000

36,000

270,000

216,000

135,000

54,000

360,000 288,000

180,000

72,000

BTUH Inputs and Capacities by Altitude in Canada

Altitude

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies

to AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Feet

Meters

H102

H125

H150

0-2000

0-610

100,000

80,000

25,000

10,000

125,000

100,000

25,000

15,000

150,000 120,000

37,500

15,000

2001-4500

611-1373

90,000

72,000

22,500

9,000

112,500

90,000

22,500

13,500

135,000 108,000

33,750

13,500

Feet

Meters

H175

H202

H402

0-2000

0-610

175,000

140,000

50,000

20,000

200,000

160,000

50,000

20,000

400,000 320,000

100,000

40,000

2001-4500

611-1373

157,500

126,000

33,750

18,000

180,000

144,000

45,000

18,000

360,000 288,000

90,000

36,000

Feet

Meters

H502

H602

H702

0-2000

0-610

500,000

400,000

150,000

60,000

600,000

480,000

150,000

60,000

700,000 560,000

175,000

70,000

2001-4500

611-1373

450,000

360,000

90,000

54,000

540,000

432,000

135,000

54,000

630,000 504,000

157,500

63,000

Feet

Meters

H802

0-2000

0-610

800,000

640,000

200,000

80,000

2001-4500

611-1373

720,000

576,000

180,000

72,000

BTUH Inputs and Capacities by Altitude in Canada

Altitude

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Feet

Meters

G150

G225

G300

0-2000

0-610

150,000

136,500

75000

30,000

225,000

204,750

112500

45,000

300,000 273,000

150,000

60,000

2001-4500

611-1373

135,000

122,850

67500

27,000

202,500

184,275

101250

40,500

270,000 245,700

135,000

54,000

BTUH Inputs and Capacities by Altitude in Canada

Altitude

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies

to AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Feet

Meters

G302

G372

G452

0-2000

0-610

300,000

273,000

75,000

30,000

375,000

341,250

112,500

45,000

450,000 409,500

112,500

45,000

2001-4500

611-1373

270,000

245,700

67,500

27,000

337,500

307,125

67,500

40,500

405,000 368,550

101,250

40,500

Feet

Meters

G525

G602

0-2000

0-610

525,000

477,750

131,250

52,500

600,000

546,000

150,000

60,000

2001-4500

611-1373

472,500

429,975

118,125

47,250

540,00

491,400

135,000

54,000