Reznor VC series infrared heaters High altitude conversion instructions User Manual

Page 8

Advertising
background image

8

USA

Natural Gas 2001– 4000 ft (611-1220m)

Size

60

80

100 125

150

170

200

“WC 4.0

3.3

3.3

3.9

4.0

3.2

3.3

mbar 10.0

8.2

8.2

9.7

10.0

8.0

8.2

CANADA Natural Gas 2001– 4500 ft (611-1370m)

Size

60

80 100 125 150

170

200

“WC

4.0 3.3 3.3 3.9

4.0

3.2

3.3

mbar

10.0 8.2 8.2 9.7 10.0

8.0

8.2

USA Natural Gas 4001– 6000 ft (1221-1829m)

Size

60

80

100

125

150

170 200

“WC

4.0

3.3

3.3

3.9

4.0

3.2

3.3

mbar 10.0

8.2

8.2

9.7

10.0

8.0

8.2

Natural Gas 6001– 10000 ft (1830-3048m)

USA

Size

60

80

100

125

150

170

200

“WC 3.9

3.2

3.2

3.8

3.9

3.1

3.2

mbar 9.7

8.0

8.0

9.5

9.7

7.7

8.0

Orifice Pressure Adjustment (VPS/VCS)