Reznor VC series infrared heaters High altitude conversion instructions User Manual

Page 9

Advertising
background image

9

USA

Natural Gas 2001– 4000 ft (611-1220m)

Size

60

80

100

125

150

170

200

“WC Hi

4.1

3.7

4.7

4.3

4.2

3.8

3.3

mbar Hi 10.2

9.2

11.7

10.7

10.5

9.5

8.2

“WC Lo

2.3

2.1

2.0

2.5

2.0

2.2

2.0

mbar Lo

5.7

5.2

5.0

6.2

5.0

5.5

5.0

USA

Natural Gas 4001– 6000 ft (1221-1829m)

Size

60

80

100

125

150

170

200

“WC Hi

4.1

3.7

4.7

4.3

4.2

3.8

3.3

mbar Hi 10.2

9.2

11.7

10.7

10.5

9.5

8.2

“WC Lo

2.3

2.1

2.0

2.5

2.0

2.2

2.0

mbar Lo

5.7

5.2

5.0

6.2

5.0

5.5

5.0

USA

Natural Gas 6001– 10000 ft (1830-3048m)

Size

60

80

100

125

150

170

200

“WC Hi

4.0

3.6

4.6

4.2

4.1

3.7

3.2

mbar Hi 10.0

9.0

11.5

10.5

10.2

9.2

8.0

“WC Lo

2.2

2.0

1.9

2.4

1.9

2.1

1.9

mbar Lo

5.5

5.0

4.7

6.0

4.7

5.2

4.7

CANADA

Natural Gas 2001– 4500 ft (611-1371m)

Size

60

80

100

125

150

170

200

“WC Hi

4.1

3.7

4.7

4.3

4.2

3.8

3.3

mbar Hi

10.2

9.2

11.7

10.7

10.5

9.5

8.2

“WC Lo

2.3

2.1

2.0

2.5

2.0

2.2

2.0

mbar Lo

5.7

5.2

5.0

6.2

5.0

5.5

5.0

Orifice Pressure Adjustment (VPT/VCT)