INSTALLATION

INSTRUCTION

DOWNFLOW ECONOMIZER # 558870

PACKAGE EQUIPMENT MODELS

*R6G(D,F) 024*–060* / *R8GD 036*-060*

*P6SD 024*-060* / *Q6SD 024*-060*

RE TURN FIL TER RE PLACE MENT (16 x 20 x 1)

Step 1:
Remove 2 screws on filter access panel on barometric
relief hood.

Step 2:
Lift blade to allow filter to be removed

Step 3:
Slide filter out through hood and replace with new filter.

Step 4:
Replace top of hood and secure with screws.

(See pictures below and to the right)

USE HOLE WITH BUSHINGS

REMOVE FOR FILTER ACCESS

REMOVE TWO SCREWS TO
REMOVE TOP OF HOOD

Notes for use with heat pumps

Economizer Configuration Instructions for use with O/B
configurable thermostats with Heat pumps

When this economizer is used in conjunction with a heat
pump, special attention must be given to the thermostat.
Some newer digital thermostats only allow a single choice of
an "O" or "B" signal. When configuring this economizer for
use with one of these thermostats, the thermostat must be
configured to provide an "O" signal to ensure proper
operation of the reversing valve. Additionally the
economizers relay must be reconfigured to account for the
loss of the "B" signal. To do this, reverse the connections of
the white and yellow wires on relay terminal numbers 1 and 4.
Then reverse the green and grey wires at the relay terminal
numbers 3 and 6. Ensure that all connections are secure and
follow the regular installation instructions for all other
operations. (See diagram to the right.)

Note: Some unit wiring diagrams may still show the "B"
input signal to the unit. On these systems, connect the
applicable wires to the thermostats "O" signal.