40KMC------310/ 40KMQ------310

GB - 3

E N G L I S H

Indoor unit LEDs

Information concerning indoor unit operation, timer status and
diagnostic is given by 3 LEDs located on the unit.

THE GREEN LED (P) shows the following conditions:

- Fault codes (diagnostic);
- During normal operation, the LED is lit.

Once a failure occurs, the LED flashes at intervals of 0.5
seconds. The fault code is deduced from the number of times
the LED flashes. Between one flash cycle and the next a pause
of 5 seconds elapses.

THE RED LED (Q) gives the following information:

- During normal operation, the LED is OFF;
- During defrost the LED is lit;
- During the test for wired connection, the LED flashes at 0.1

second intervals.

THE YELLOW LED (R) shows the operation in timer mode.

During this operation the LED is lit.
If the timer mode is active and the unit is immediately
restarted after a stop, this LED flashes until a new signal is
sent to the unit.

In case the Room Controller is not working, obtain a qualified
service personnel.

Unit warning lights and controls - Fault code

P : Green LED

Q : Red LED

R : Yellow LED

S : Remote control

signal receiver

For a good operation of the
air conditioner it is
recommended to carry out
checks and maintenance
as indicated.
Recommended
maintenance intervals may
vary depending on the
installation environment,
e.g. dusty zones, etc.

(1) Increase frequency in

dusty zones.

(2) Operations to be

carried out by qualified
service personnel.
Refer also to
“Installation Manual”.

Table II: Periodical checks

Indoor unit

Every month

Every 4 months

Every year

Clean air filter (2)

(1)

Clean drain pipe (2)

Outdoor unit

Every month

Every 4 months

Every year

Clean outdoor coil from outside

Clean outdoor coil from inside (2)

Blow air over electric parts (2)

Check electric connection tightening (2)

Clean fan wheel (2)

Check fan tightening (2)

Clean drain pan (2)

Fault code

Once a failure occurs with the indoor unit in operation, the green
unit LED flashes at intervals of 0.5 seconds.
The fault code is deduced from the number of times the green
LED flashes, blocking unit operation.
Between one flash cycle and the next one, a pause of 5 seconds
elapses.

* with enabled code

Table IX: Fault code

Code

Description

3

Room air sensor fault

2

Condensate discharge pump

4

Indoor unit coil sensor fault

6*

Filter dirty

7

Outdoor unit failure

10

EEPROM corrupt

11

Card serial number damaged

12

Address / zone incomplete

13

Gas flow distributor corrupt

14

Outdoor air thermistor