Configuring Module
This section describes how to configure the 5635 Annunciator that has been added to
the system. Each SBUS device requires a unique address. 5635 Series DIP switch
S21 is used to set the address. This address will be displayed on the LCD display as
the Station ID number.
4.7.1
Assigning Module IDs
When installing the 5635 you must use the DIP switches on the module to assign an
ID# to the module. A maximum of 2 devices can be connected to the FACP SBUS
communication circuit. The SBUS device address needs to be set to 01or 02.
Note: Note that 00 is not a valid address.
Figure 4-13 shows the DIP switch positions and their correlation to a numerical ID.
Figure 4-13 DIP switch settings
ID Number
(Address)
(not valid)
00
01
DIP Switch