Model 5700 installation and operation manual – SilentKnight 5700 User Manual

Page 24

Advertising
background image

Model 5700 Installation and Operation Manual

151295

3-7

SK-Zone

(50 max.)

1

Aux Pwr

Standby: 12 mA

mA

mA

Alarm: 90 mA

mA

mA

SLC

Standby/Alarm: .27 mA

mA

mA

SK-Zone-6

Aux Pwr

Standby: 50 mA

mA

mA

Alarm: 270 mA

mA

mA

SLC

Standby/Alarm: 2 mA

mA

mA

SLC Accessories

B200SR Sounder Base

(50 max.)

Aux Pwr

Standby: .50 mA

mA

Alarm: 35 mA

mA

SLC

Standby: .3 mA

mA

B200S Sounder Base

Aux

Standby: .50 mA

mA

Alarm (high vol) 35 mA

mA

SLC

Standby: .3mA

mA

mA

B200SR-LF Low Frequency
Sounder Base

Aux Pwr

Standby: 1 mA

mA

Alarm: 125 mA

mA

B200S-LF Low Frequency
Sounder Base

Aux Pwr

Standby .55 mA

mA

Alarm (high vol) 140 mA

mA

SLC

Standby .30 mA

mA

B224RB Relay Base

Standby/Alarm: .5 mA

mA

mA

RTS151/151 KEY

Alarm: 7.5 mA

mA

RA100Z

Alarm: 10 mA

mA

SLC Isolator Devices

SK-Iso (Isolator Module)

(100 max.)

Standby/Alarm: .45 mA

mA

mA

B224BI Isolator Base

(50 max.)

Standby/Alarm: .5 mA

Accessories Modules

5860 Remote Fire Alarm
Annunciator

(8 max)

Standby

20mA

mA

Alarm

25mA

mA

5824 Serial / Parallel Module

(2 max.)

Standby/Alarm: 45 mA

mA

mA

5496 Notification Power
Expander

(8 max.)

Standby/Alarm: 10 mA

mA

mA

5895XL

Standby/Alarm: 10 mA

mA

mA

5865-4 LED Annunciator

(with reset and silence switches)

(8 max.)

Standby: 35 mA

mA

Alarm: 145 mA

mA

5865-3 LED Annunciator

Standby: 35 mA

mA

Alarm: 145 mA

mA

5880 Generic LED Driver
Module

Standby: 35 mA

mA

Alarm: 200 mA

mA

5883 Relay Interface

(32 max.)

Standby: 0 mA

mA

Alarm: 220 mA

(22 mA per relay)

mA

A

Total System Current

Auxiliary Devices

2

Refer to devices manual for current rating.

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Table 3-2: Current Calculation Worksheet for SK Devices

Device

# of

Devices

Current per Device

Standby

Current

Alarm

Current

Advertising