Model 5700 installation and operation manual – SilentKnight 5700 User Manual
Page 24

Model 5700 Installation and Operation Manual
151295
3-7
SK-Zone
(50 max.)
1
Aux Pwr
Standby: 12 mA
mA
mA
Alarm: 90 mA
mA
mA
SLC
Standby/Alarm: .27 mA
mA
mA
SK-Zone-6
Aux Pwr
Standby: 50 mA
mA
mA
Alarm: 270 mA
mA
mA
SLC
Standby/Alarm: 2 mA
mA
mA
SLC Accessories
B200SR Sounder Base
(50 max.)
Aux Pwr
Standby: .50 mA
mA
Alarm: 35 mA
mA
SLC
Standby: .3 mA
mA
B200S Sounder Base
Aux
Standby: .50 mA
mA
Alarm (high vol) 35 mA
mA
SLC
Standby: .3mA
mA
mA
B200SR-LF Low Frequency
Sounder Base
Aux Pwr
Standby: 1 mA
mA
Alarm: 125 mA
mA
B200S-LF Low Frequency
Sounder Base
Aux Pwr
Standby .55 mA
mA
Alarm (high vol) 140 mA
mA
SLC
Standby .30 mA
mA
B224RB Relay Base
Standby/Alarm: .5 mA
mA
mA
RTS151/151 KEY
Alarm: 7.5 mA
mA
RA100Z
Alarm: 10 mA
mA
SLC Isolator Devices
SK-Iso (Isolator Module)
(100 max.)
Standby/Alarm: .45 mA
mA
mA
B224BI Isolator Base
(50 max.)
Standby/Alarm: .5 mA
Accessories Modules
5860 Remote Fire Alarm
Annunciator
(8 max)
Standby
20mA
mA
Alarm
25mA
mA
5824 Serial / Parallel Module
(2 max.)
Standby/Alarm: 45 mA
mA
mA
5496 Notification Power
Expander
(8 max.)
Standby/Alarm: 10 mA
mA
mA
5895XL
Standby/Alarm: 10 mA
mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA
mA
Alarm: 145 mA
mA
5865-3 LED Annunciator
Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 Generic LED Driver
Module
Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface
(32 max.)
Standby: 0 mA
mA
Alarm: 220 mA
(22 mA per relay)
mA
A
Total System Current
Auxiliary Devices
2
Refer to devices manual for current rating.
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Table 3-2: Current Calculation Worksheet for SK Devices
Device
# of
Devices
Current per Device
Standby
Current
Alarm
Current