3 conventional initiation circuits, 1 class b inputs, 2 class a inputs – SilentKnight 5895XL 6A Intelligent Remote Power Supply User Manual
Page 29: 3 conventional initiation circuits -9, Class a inputs -9

Hardware Installation
151142
3-9
3.5.3
Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for Class A
(Style D) or Class B (Style B) configurations.
3.5.3.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations,
directly to the I/O circuits of the 5895XL panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 3-10.
2. Configure the circuit through programming (see Section 7.4 of the Installation Manual
P/N 151209).
Figure 3-10 Class B Input Switches
3.5.3.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations,
directly to the I/O circuits of the 5895XL panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 3-11.
UL Listed EOL
Model 7628
4.7 k