IPGSM-4G Commercial Fire Communicator – Installation and Setup Guide

– 12 –

IPGSM-4G Trouble Detection Information

Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4G, and Telco 2 is used by the IPGSM-

4G to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if

there are no faults in the Communicator.

Fault Condition

Indication to Fire Panel

PowerBoost1 fault

Telco 2 is cut.

Communicator fault

•

Failure of the communications path when

IP only or GSM only is programmed as a

communications path.

Telco 2 is cut.

•

Failure of both communications paths

when IP&GSM is programmed as a com-

munications path.

Telco 1 and 2 are cut.

Dialer Capture Module buffer is full.

Hang up. (Panel will retry, giving the buffer a chance

to empty.)

IPGSM-4G Specifications

ITEM

SPECIFICATION

Cabinet Dimensions:

Width 12 3/4 inches, Height 14 7/8 inches, Depth 3 inches

Transformer: N8167

Primary – 120VAC, 60Hz, Secondary – 18VAC, 50VA

Battery:

12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.

Battery Charging Current:

maximum 1A

Battery Discharge Current: standby 230mA, active 950mA

Environment:

Operating temperature: –20º to +55ºC, for UL installations 0ºC to

+49ºC
Storage temperature: –40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing, for UL instal-

lations 0% to 93%
Altitude: to 10,000 ft. operating, to 40,000 ft. storage

Supervision:

The Radio (communicator), battery, and AC power, conditions are

monitored by the cabinet indicator LEDs:
RADIO TROUBLE lights when any of these conditions exist.
•

Both IP and GSM communication paths are lost.

•

Communicator radio is not registered.

•

Old Alarm Time has been exceeded. (Message has not been de-

livered within the fixed 10 minute window.)

LOW BATTERY lights when the battery voltage is less than 11.5VDC.
AC LOSS lights when the AC power is less than 90VAC.