General information, Package contents, Compatible fire panels – SilentKnight IPGSM-4G User Manual

Page 3: Operation, Installation, Ul compliance

Advertising
background image

IPGSM-4G Commercial Fire Communicator – Installation and Setup Guide

– 1 –

General Information

The IPGSM-4G Commercial Fire Communicator (henceforth referred to as IPGSM-4G) is a commercial Fire Alarm com-

municator that allows a Fire panel that previously reported by POTS to be upgraded to a system that uses the internet

or cellular means to connect to a central station.
This dual path communicator connects directly to the primary and secondary communication ports of a Fire panel's Dig-

ital Alarm Communicator Transmitter (DACT). It offers three selectable reporting paths which include; Cellular only, IP

only, or IP primary/cellular backup. In addition, the communicator’s power module (PowerBoost1) monitors and re-

ports AC power loss, and low battery conditions. All signals from the IPGSM-4G communicator panel are delivered to

Honeywell's AlarmNet Network Control Center, which routes the information to the appropriate central station.

Package Contents

•

Red Fire Cabinet and Back Plate

•

Antenna and Mounting Adapter

•

LED Display board

•

Cam Lock with Key

•

PowerBoost1

•

Mounting Rails (for above)

•

Dialer Capture Module

•

Battery harness

•

Hardware Bag

•

Communicator

•

Wall Outlet Box (P/N K14358)

•

Transformer, 18VAC (N8167)

•

50 ohm cable assembly (for antenna)

•

Ferrite Filter

Compatible Fire Panels

The IPGSM-4G is compatible with Fire Panels that use the Contact ID communication format as described in the SIA

DC-05 Standard.
After completing the field installation, verify communications with the central station is successful by sending several

events. Also, get confirmation that these events were received.

Operation

The IPGSM-4G replaces the fire panel's POTS communications path. When an event occurs, the fire panel goes off-

hook to dial the central station. The IPGSM-4G detects the off-hook condition and provides the fire panel with a dial

tone. When the fire panel detects the dial tone, it begins dialing the central station. The IPGSM-4G considers the three

second period after dialing as the number dialing has been completed. After the dialing is completed, the Dialer Cap-

ture Module returns a handshake to the fire panel.
The fire panel then sends the contact ID reports to the IPGSM-4G, which in turn sends a kiss-off after the report is suc-

cessfully received from the fire panel. Within the IPGSM-4G, the Dialer Capture Module sends the contact ID reports

over the ECP bus to the Communicator. When all the reports are sent, the fire panel goes on-hook. The IPGSM-4G

then transmits the messages to the central station (either over the internet or the GSM network).

Installation

UL Compliance

To meet UL864/NFPA, ensure the following:

•

IPGSM-4G must be installed in accordance with NFPA (National Fire Protection Association) standards 70

and 72.

•

IPGSM-4G must be mounted in the same room and within 20 feet of the fire panel.

•

The Telco line wiring and the Power Transformer wiring must be routed through conduit.

•

IPGSM-4G, and all equipment used for the IP connection (such as the router, hub, modem, etc.) shall be UL

Listed, must be powered from an un-switched branch circuit, and be provided with appropriate standby power.

•

IPGSM-4G must use a 7AH battery (not supplied) to provide 24-hour backup capability.