Carrier AQUAZONE RVC User Manual

Page 28

Advertising
background image

28

Table 9 — 50RHC,RVC Blower Performance

*Size 006 is available in 50RHC unit only.

†Size 041 is available in 50RVC unit only.

NOTES:

1. Gray areas denote ESP (external static pressure) where operation is not

recommended.

2. Units factory shipped on medium speed. Other speeds require field

selection.

3. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v

for 208-230 v units.

4. All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed.

5. Only two-speed fan (H & M) available on 575-v units.
6. For wet coil performance first calculate the face velocity of the air

coil (Face Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for veloci-
ties of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12 in. wg, and 500 fpm by 0.16 in. wg.

7. Airflow in cfm with net dry coil and clean air filter.

Table 10 — 50RVC Blower Performance with Hot Water Reheat (HWR) Option

50RHC,RVC

UNITS

RATED

CFM

MIN

CFM

FAN

SPEED

AIRFLOW (Cfm)

External Static Pressure (in. wg)

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.0

1.10

1.20

1.30

006*

220

150

HI

310

300

290

280

270

250

230

210

180

MED

260

250

240

230

210

200

190

150

LO

210

200

190

180

160

150

009

325

225

HI

410

400

380

360

350

330

320

300

280

MED

390

370

360

340

320

310

290

280

260

LO

340

330

322

310

300

280

260

250

220

012

400

300

HI

470

460

450

440

430

420

400

390

380

320

MED

420

410

400

390

380

370

360

350

340

LO

360

360

350

340

320

320

310

300

290

018

600

450

HI

760

740

720

710

700

680

650

600

550

460

MED

700

690

680

670

660

650

630

620

600

560

520

430

LO

620

610

600

590

580

570

560

540

520

490

460

018

High Static

600

450

HI

790

780

770

760

750

730

710

690

650

530

430

MED

750

740

720

710

700

690

670

670

660

650

630

600

490

390

LO

670

660

640

630

620

610

600

590

580

580

570

530

420

024

800

600

HI

1000

970

930

870

770

690

MED

1010 1000

990

980

960

940

920

900

880

860

830

770

700

600

LO

820

810

800

790

780

770

760

750

730

720

700

650

600

024

High Static

800

600

HI

1030

950

840

700

MED

1040 1010

970

890

750

620

LO

1030 1010

980

960

930

900

870

790

710

030

1000

750

HI

1160 1130 1100 1070 1030

950

840

MED

1250 1230 1200 1180 1150 1120 1090 1070 1040 1010

970

890

750

LO

1120 1100 1070 1050 1030 1010

980

960

930

900

870

790

710

030

High Static

1000

750

HI

1160 1040

920

800

750

MED

1130 1080 1030

930

820

750

LO

1050 1040 1030 1010

990

980

960

940

910

880

840

750

036

1200

900

HI

1520 1500 1480 1460 1430 1400 1370 1350 1320 1270 1210 1110

960

840

MED

1150 1150 1140 1140 1130 1130 1120 1110 1100 1070 1040

940

LO

1010 1010 1000 1000

990

990

980

980

970

950

930

036

High Static

1200

900

HI

1530 1500 1470 1400 1290 1170

960

MED

1360 1350 1340 1330 1320 1310 1300 1280 1260 1250 1230 1150 1070

910

LO

1030 1020 1010 1010 1000 1000

990

980

960

950

930

041†

1325

950

HI

1380 1370 1350 1330 1300 1260 1220 1170 1120 1080 1040

890

MED

1230 1220 1200 1190 1180 1150 1120 1080 1030

990

950

LO

1040 1030 1010 1000

990

970

950

042

1350

1050

HI

1640 1610 1580 1550 1520 1490 1450 1410 1370 1330 1290 1190 1100

MED

1490 1470 1440 1420 1390 1370 1340 1310 1270 1230 1190 1120 1010

LO

1140 1140 1130 1130 1120 1110 1100 1080 1060 1010

042

High Static

1350

1050

HI

1550 1540 1520 1500 1470 1460 1450 1380 1240 1080

MED

1390 1380 1370 1360 1350 1340 1320 1310 1300 1280 1250 1180 1080

LO

048

1600

1200

HI

1980 1950 1910 1860 1800 1740 1680 1490 1280 1280

MED

1940 1920 1900 1880 1860 1820 1770 1740 1710 1660 1600 1410 1000

LO

1770 1750 1730 1710 1690 1670 1650 1610 1570 1510 1450 1330

048

High Static

1600

1200

HI

2060 2040 2010 1960 1880 1790 1660 1510

MED

2050 2050 2040 2020 1990 1970 1940 1920 1890 1860 1830 1780 1710 1620 1490 1320

LO

1850 1850 1840 1830 1810 1800 1780 1760 1730 1700 1670 1600 1510 1380 1220

060

2000

1500

HI

2240 2240 2230 2220 2200 2160 2120 2090 2060 2040 2010 1960 1880 1790 1660 1510

MED

2050 2050 2040 2020 1990 1970 1940 1920 1890 1860 1830 1780 1710 1620 1490

LO

1850 1850 1840 1830 1810 1800 1780 1760 1730 1700 1670 1600 1510

060

High Static

2000

1500

HI

2400 2400 2390 2380 2370 2360 2340 2320 2300 2270 2240 2200 2130 2060 1980 1890 1790 1660 1500

MED

2160 2160 2150 2150 2140 2110 2080 2060 2040 2030 2020 1980 1930 1880 1490 1750 1660 1530

LO

1930 1930 1920 1920 1910 1900 1890 1890 1880 1870 1850 1830 1800 1750 1700 1620 1530

REHEAT EXTERNAL STATIC PRESSURE (ESP) LOSS

COIL FACE VELOCITY

(fpm)

018, 024, 030

(in. wg)

036, 042

(in. wg)

048, 060

(in. wg)

200

0.060

0.049

0.038

250

0.070

0.055

0.040

300

0.090

0.068

0.045

350

0.124

0.091

0.059

400

0.164

0.129

0.094

450

0.252

0.221

0.189

500

0.380

0.350

0.320

NOTE: For 50RVC units with HWR, calculate coil face velocity of the entering air. Find the
external static pressure loss for the reheat application. This loss includes the wet coil loss.

Advertising
This manual is related to the following products: