Programming 151204
4-14
4.2.11
5280 Outputs
Figure 4-13 illustrates, in more detail, the programming flow when in the SK-5280 outputs menu.
Figure 4-13 5280 Outputs Programming Menu
If Zones 1-10 is selected then the SK-5280 will output when alarms and troubles occur for zones 1 through 10. If
Zones 11-20 is selected then SK-5280 will output when alarms and troubles occur for zones 11 through 20. If
Zones 21-30 is selected then the SK-5280 will output when alarms and troubles occur for zones 21-30.
If System is selected then the SK-5280 will output as shown in Table 4-3 for the following system conditions:
Table 4-3: System Outputs
SK-5280 Output
Terminal
Output For:
A1
Fire Alarm
A2
Waterflow Alarm
A3
Supervisory
A4
Aux Alarm
A5
Prealarm
A6
Trouble
A7
Communications Fail
A8
Communicating
A9
Alarm Silenced
A10
Trouble Silenced
T1
Low AC
T2
Low Battery
T3
Relay 1 Active
T4
Relay 2 Active
T5
Relay 3 Active
T6
Relay 4 Active
T7
NAC 1 Active
T8
NAC 2 Active
T9
NAC 3 Active
T10
NAC 4 Active