Manual changeover with deluxe d controller, Typical wiring schematics (cont) – Carrier AQUAZONE 50KQL-1PD User Manual

Page 26

Advertising
background image

26

Typical wiring schematics (cont)

MANUAL CHANGEOVER WITH DELUXE D CONTROLLER

FP2

CAP

PB

DELUXE D
CONTROL

BR 2
(HI)

UMT

PBS

OS

GROUND
LOG

TRANSFORMER

CR

BR 1
(LO)

S

JW1
LP

TEST

PINS

JW2
FP2

JW3
FP1 LOW

LOW

N.O.

ACC1
FUNCTIONS

ACC2
FUNCTIONS

H: HI FAN/DEHUMID
NOT USED

OFFON

S2

DIP SWITCH PACKAGE

S1

DIP SWITCH PACKAGE

OFFON

PM: DISABLE/ENABLE
UNIT STAGE: 2/1
T’STAT: HEAT COOL/HEAT PUMP
RV ON B/RV ON O
DEHUMID/NORMAL
NOT USED
BOILERLESS: ENABLE/DISABLE
BOILERLESS: 40

°F/50°F

SEE
NOTE 4

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

Y1

O/W2

G

R

C

AL1

W1

AL2

A

P3

R

C

ALARM

RELAY

SEE

NOTE 6

SEE
NOTE 7

NSB

ESD

OVR

H

P2

C

R

Y2

P1

R

R

COM

NC2

NO2

COM

NC1

NO1

RELAY

ACC1

RELAY

ACC2

1
2

3

4

5

6

7

8

COM2

COM1

R C S

C

JW4

AL2

DRY

RED

RED

2

3

2A

ORG

3A

RED GRY

YEL

ORG

YEL

UMT

2

3

PBS

1A

1B

YEL YEL YEL

ORG

DM

BRN

BRN

RED

TIME CLOCK

CLOSED-UNOCCUPIED

BRN

GRY

YEL

WHT

WV

WHT

RED

OS

NLL

GRY

GRY

PBS

RED

5

6

5A

6A

RED

7

7A

RED

GRY

P7

P6

CCG

24V
DC

EH1

EH2

BRN

CC

YEL

CR

1

COMPR

RELAY

0

FAN E N A B L E

RELAY

STATUS

TEST

FAULT

G

DELUXE D

MICROPROCESSOR

CONTROL LOGIC

1
2

RV RELAY

3
4

5

7

9

10

HP

L O C

FP1

RV

C O

HP

LOC

FP1

BRN

ORG

YEL

VIO

SEE

NOTE 4

FP2

CO

Y

R

GRY

C O M

NO

NC

COM

NO

FAN

S P E E D

R E L A Y

GRY

RED
RED

12

8

6

NOT USED

RVS

BLU

BRN

VIO

GRY

YEL

BLU

1

BLK

RED

BLK

ORG
230V

24V

TRANS

CB*

POWER SUPPLY

REFER TO DATA PLATE

USE COPPER CONDUCTORS ONLY.

SEE NOTE 2

REFER TO DISCONNECT

BOX FOR OPTIONAL

POWER SUPPLY CONNECTION

GROUND

L2

L1

OPTIONAL
CORD
CONNECTION

RED

NEUTRAL ON 265V
SYSTEMS

L2 (ribbed)

GROUND

L1 (plain)

PB
1

2

H

C

F

CAP

RED

RED

6

8

2

4

BLK

BLK

R

S

C

CR

BLU

COMPRESSOR

BRN

YEL

2

1

BM

B (HIGH)

A (LOW)

BLK

115
208
230
265

WHT
RED
ORG
BRN

LEAD COLOR

VOLTAGE

TRANSFORMER PRIMARY

LEAD COLORS

GRY

SEE
NOTE 3

PUSH BUTTON SWITCH ATTRIBUTES

X = CLOSED

O = OPEN

TERMINALS

1

2

3

4

5

6

7

8

1A 1B 2A 3A 4A 5A 6A 7A 8A

STOP

X O O O O O O O O

FAN ONLY X O O O O X O O O

LOW COOL O X X O O O X O O

HIGH COOL O X X O O O O X O

LOW HEAT X O O X X O X O O

HIGH HEAT X O O X X O O X X

BLOWER MOTOR WIRING

UNIT SIZE

POLE A

POLE B

07

5

3

09

5

4

12

4

3

15

4

3

19

4

3

AL

—

Alarm Relay Contacts

BM

—

Blower Motor

BR

—

Blower Relay

CAP

—

Capacitor

CB

—

Circuit Breaker

CO

—

Sensor, Condensate Overflow

CR

—

Compressor Relay

DM

—

Damper Motor

FP1

—

Sensor, Water Coil Freeze Protection

FP2

—

Sensor, Air Coil Freeze Protection

HP

—

High-Pressure Switch

JW1

—

Jumper Wire for Alarm

LOC

—

Loss of Charge Pressure Switch

NLL

—

Night Low Limit Switch

OS

—

Override Switch

PB

—

Power Terminal Block

PBS

—

Push Button Switch

PM

—

Performance Monitor

RVS

—

Reversing Valve Solenoid

TRANS

—

Transformer

UMT

—

Unit Mounted Thermostat

WV

—

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring

LEGEND

Printed Circuit Trace

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

*Optional wiring.

NOTES:

1.

Compressor and blower motor thermally protected
internally.

2.

All wiring to the unit must comply with local codes.

3.

Transformer is wired to 115-V (WHT) lead for 115/1/60
units, 265-V (BRN) lead for 265/1/60 units or 208-V
(RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1 and insu-
late RED lead.
Transformer is energy limiting or may have circuit
breaker.

4.

FP1 thermistor provides freeze protection for WATER.
When using ANTI-FREEZE solutions, cut JW3 jumper.

5.

Typical unit-mounted thermostat wiring shown.

6.

24-V alarm signal shown. For dry alarm contact, cut AL2
DRY (JW4) jumper and dry contact will be available
between AL1 and AL2.

7.

Transformer secondary ground via Deluxe D board
standoffs and screws to control box. (Ground available
from top two standoffs as shown.)