Automatic changeover with complete c controller – Carrier AQUAZONE 50KQL-1PD User Manual

Page 27

Advertising
background image

27

AUTOMATIC CHANGEOVER WITH COMPLETE C CONTROLLER

COMPLETE

C

CONTROL

UMT

BR1

BR2

PBS

CR

CAP

PB

GROUND

TRANSFORMER

RED

3

4

BRN

YEL

YEL

YEL

RED

6A

5A

RED

5

RED

RED

PBS

RED

RED

ORG

BRN

YEL

5

3A

UMT

2

3

1

6

7A

BRN

7

YEL

YEL

ORG

6

DM

ORG

RED

BRN

BRN
BRN

YEL

BR1

BR2

BLU

WV

SEE
NOTE 7

BR

BRG

CCG

R

Y

Y

W

O

G

R

C

AL1

AL2

A

P1

ALARM

RELAY

C

SEE
NOTE 6

JW1

JW3

FP1

JW2

FP2

SEE
NOTE 4

TEST PINS

SEE
NOTE 7

YEL

BRN

CC

YEL

COMPR.
RELAY

STATUS
LED

G

COMPLETE C

MICRO-

PROCESSOR

CONTROL

LOGIC

HP

LOC

FP1

FP2

RV

CO12

P2

24V
DC

EH1
EH2

P3

CO

1
2
3

4
5
6

7

8

9

10

1

0

HP

LOC

FP1

FP2

RVS

CO

SEE
NOTE 4

RED

RED

BLU

BRN

GRY

GRY

VIO

VIO

BRN

ORG

NOT USED

DIP SWITCH

OFF ON

PM: DISABLED/
ENABLED
STAGE 2: 2/1
NOT USED
NOT USED

FP1/FP2
FAULTS: 3/1

1

2
3
4

5

BLK

ORG
230V

24V

TRANS

CB*

POWER SUPPLY

REFER TO DATA PLATE

USE COPPER CONDUCTORS ONLY.

SEE NOTE 2

REFER TO DISCONNECT

BOX FOR OPTIONAL

POWER SUPPLY CONNECTION

GROUND

L2

L1

OPTIONAL
CORD
CONNECTION

RED

NEUTRAL ON 265V
SYSTEMS

L2 (ribbed)

GROUND

L1 (plain)

PB
1

2

H

C

F

CAP

RED

RED

6

8

2

4

BLK

BLK

R

S

C

CR

BLU

COMPRESSOR

BRN

YEL

BLK

BLK

BLK

2

1

5

6

7

BM

B (HIGH)

A (LOW)

RED

RED

BLK

PBS

7A

6A

5A

115
208
230
265

WHT
RED
ORG
BRN

LEAD COLOR

VOLTAGE

TRANSFORMER PRIMARY

LEAD COLORS

SEE
NOTE 3

PUSH BUTTON SWITCH ATTRIBUTES

X = CLOSED

O = OPEN

TERMINALS

1

2

3

4

5

6

7

8

1A 1B 2A 3A 4A 5A 6A 7A 8A

STOP

X

O

O

O

O

O

O

O

O

FAN ONLY

X

O

O

O

O

X

O

O

O

LOW FAN

X

O

O

X

X

O

X

O

O

HIGH FAN

X

O

O

X

X

O

O

X

X

BLOWER MOTOR WIRING

UNIT SIZE

POLE A

POLE B

07

5

3

09

5

4

12

4

3

15

4

3

19

4

3

AL

—

Alarm Relay Contacts

BM

—

Blower Motor

BR

—

Blower Relay

CAP

—

Capacitor

CB

—

Circuit Breaker

CO

—

Sensor, Condensate Overflow

CR

—

Compressor Relay

DM

—

Damper Motor

FP1

—

Sensor, Water Coil Freeze Protection

FP2

—

Sensor, Air Coil Freeze Protection

HP

—

High-Pressure Switch

JW1

—

Jumper Wire for Alarm

LOC

—

Loss of Charge Pressure Switch

PB

—

Power Terminal Block

PBS

—

Push Button Switch

PM

—

Performance Monitor

RVS

—

Reversing Valve Solenoid

TRANS —

Transformer

UMT

—

Unit Mounted Thermostat

WV

—

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring

*Optional wiring.
NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 115-V (WHT) lead for

115/1/60 units, 265-V (BRN) lead for 265/1/60
units or 208-V (RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1
and insulate RED lead.
Transformer is energy limiting or may have cir-
cuit breaker.

4. FP1 thermistor provides freeze protection for

WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.

5. Typical unit-mounted thermostat wiring shown.
6. 24-V alarm signal shown. For dry alarm con-

tact, cut JW1 jumper and dry contact will be
available between AL1 and AL2.

7. Transformer secondary ground via Complete

C board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)

LEGEND

Printed Circuit Trace

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>