Xi2 System Requirements for Roof Pitches Higher than 20 degrees

Wind Zone I

Wind Zone II Wind Zone III

5:12 6:12 7:12 9:12 5:12 6:12 7:12 9:12 5:12 6:12 7:12 9:12
34
2 2 2 2 2 2 2 2 2 2 3 3

36 2 2 2 2 2 2 2 3 2 2 3 3

38 2 2 2 3 2 2 2 3 2 3 3 3

40 2 2 2 3 2 2 2 3 3 3 3 3

42 2 2 3 3 2 2 3 3 3 3 3 3

44 2 2 3 3 2 2 3 3 3 3 3 3

46 2 3 3 3 2 3 3 3 3 3 3 4

48 2 3 3 3 3 3 3 3 3 3 3 4

50 3 3 3 3 3 3 3 3 3 3 3 4

52 3 3 3 3 3 3 3 3 3 3 4 4

54 3 3 3 3 3 3 3 3 3 3 4 4

56 3 3 3 3 3 3 3 3 3 3 4 4

58 3 3 3 3 3 3 3 3 3 3 4 4

60 3 3 3 3 3 3 3 3 3 3 4 5

62 3 3 3 3 3 3 3 3 4 4 4 5

64 3 3 4 4 3 3 4 4 4 4 4 5

66 3 3 4 4 3 3 4 4 4 4 4 5

68 3 4 4 4 3 4 4 4 4 4 5 5

70 3 4 4 4 3 4 4 4 4 4 5 5

72 3 4 4 4 4 4 4 5 4 4 5 5

74 4 4 4 5 4 4 4 5 4 5 5 5

76 4 4 4 5 4 4 4 5 4 5 5 6

78 4 4 4 5 4 4 4 5 4 5 5 6

80 4 4 4 5 4 4 4 5 4 5 5 6

Module

Length

(Feet)

101113,D974

Additional Systems:
On a single section home
the 3rd system is placed
in the middle of the
home. When using 3 or
4 systems (double and
triple sections) install
on opposite corners, if
needed, a 5th system
would be in the center of
the unit on either side.

Xi2 Longitudinal Stabilization for Wind Zone I, II & III

Single Section

Up to 16’ Nominal

Double Section

Up to 32’ Nominal

Triple Section

up to 48’ Nominal

NOTE: On triple section homes in

WZII & III an additional longitudinal

system is required. It should be

installed on the center section.

3285.402(c)(3) All new manufactured homes must have longitudinal stabilization in all wind zones.

When using longitudinal

stabilization only, systems

must be as evenly spaced

as possible, no more than

10’ from the end of the

home. Longitudinal struts

do not replace anchors on

single section homes.

Use One Strut (per end)

For WZ I

Use Two Struts (per end)

For WZ II & III

Sample Placement for Wind Zone I Shown