Carrier 50TFQ008-012 User Manual

Page 26

Advertising
background image

26

To align the fan and motor pulleys:

1. Loosen the fan pulley setscrews.
2. Slide the fan pulley along the fan shaft.
3. Make angular alignment by loosening the motor from the

mounting plate.

To adjust belt tension:

1. Loosen the fan motor mounting nuts.
2. Sizes 008 and 009 — Slide the motor mounting plate

away from the fan scroll for proper belt tension (

1

/

2

-in.

deflection with 5 to 10 lb of force) and tighten the mount-
ing nuts (see Fig. 38).
Size 012 — Slide the motor mounting plate downward to
tighten belt tension (

1

/

2

-in. deflection with 5 to 10 lb of

force). Secure the motor mounting plate nuts. See Fig. 39.

3. Adjust the bolt and nut on the mounting plate to secure

the motor in fixed position.

Table 9 — Fan Motor Performance

LEGEND

BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the

motors can be utilized with confidence. Using fan motors up to the horsepower ratings shown in
this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected.

UNIT

50TFQ

INDOOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM ACCEPTABLE

CONTINUOUS BHP*

MAXIMUM ACCEPTABLE

OPERATING WATTS

MAXIMUM

AMP DRAW

008

Standard,

Alternate

208/230

2.40

2120

6.0

460

3.0

575

3.0

High Static

208/230

3.70

3313

11.7

460

5.5

575

5.5

009

Standard

208/230

2.40

2120

6.0

460

3.0

575

3.0

High Static

208/230

3.70

3313

11.7

460

5.5

575

5.5

012

Standard

208/230

2.40

2120

6.0

460

3.0

575

3.0

Alternate

208/230

2.90

2615

8.6

460

3.9

575

3.9

High Static

208/230

5.25

4400

17.3

460

8.5

575

8.5

MOTOR MOUNTING

PLATE NUTS

Fig. 38 — Typical Belt-Drive Motor Mounting for

Size 008 and 009

Fig. 39 — Typical Belt-Drive Motor Mounting for

Size 012

Fig. 40 — Indoor-Fan Pulley Adjustment

Advertising