Table 4 — Electrical Data

UNIT

38AQS

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE RANGE

COMPRESSOR

OFM

POWER SUPPLY

MINIMUM DISCONNECT

Min

Max

RLA

LRA

FLA

MCA

MAX FUSE OR

HACR BRKR AMPS

FLA

LRA

008

208/230-3-60

187

254

31.5

160

3.1

42.5

50

45

177

460-3-60

414

508

15.7

80

1.4

21.0

25

25

89

220-3-50

198

242

39.7

198

3.1

52.7

70

55

205

400-3-50

360

440

19.9

99

1.4

26.3

35

30

106

LEGEND

FLA

— Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

NEC

— National Electrical Code (U.S.A.)

OFM

— Outdoor Fan Motor

RLA

— Rated Load Amps

(60 Hz Only)

(60 Hz Only)

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=

457

(AB) 457

Ϫ 452 = 5 v

(BC) 464

Ϫ 457 = 7 v

(AC) 457

Ϫ 455 = 2 v

Maximum deviation is 7 v.
Determine percent voltage imbalance

7

% Voltage Imbalance = 100

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more
than

2%,

contact

your

local

electric

utility

company

immediately.

7