APPENdIx A: TERmINAL CORRESPONdANCE

The terminals of an VT8600 are identified diifferently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondance of functions between the terminals of the VT7000
series and the VT8600 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller
with a VT8600 Room Controller.

VT7000

VT8600

Terminal name

Terminal ID

Terminal name

Terminal ID

Binary Input 1

BI1

Universal Input 16

UI16

Binary Input 2

BI2

Universal Input 17

UI17

Universal Input 3

UI3

Universal Input 19

UI19

Sensor Common

Scom

Terminal 18 Common

COM

Remote Sensor

RS

Universal Input 20

UI20 - RS

Sensor Common

Scom

Terminal 21 Common

COM

Mix/Supply Sensor

MS

Universal Input 22

UI22 - SS

APPENdIx B: POWER OUTAGE CLOCk RESET

In the event of a power outage, VT8600 Room Controllers will retain the correct time as long as the duration of the power outage is
not prolonged. Depending on the duration of the power outage, the Room Controller's internal clock may need to be updated or reset
completely. The following table gives an indication of the expected clock performance after a power outage of a given duration.

Outage duration

Room Controller behaviour

0 - 24 hours

Clock functions are normal

24 - 36 hours

Clock accuracy not guaranteed, time may need to be adjusted

36 - 72 hours

Clock no longer increments and will need to be adjusted when power is
restored.

72+ hours

Clock functions are fully reset, and will need to be reinitialized as per a
new installation.