Vt8600, Vt8600 series installation guide, Remote sensor accessories – Viconics VT8600 Installation Guide User Manual

Page 7: Series controller, Remote wiring 1 sensor, S2-1= on, s2-2=on

Advertising
background image

VT8600 Series

Installation Guide

7

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0435-01

www.viconics.com

February 2015

©

2

01

5 V

ic

onic

s T

ec

hno

lo

gi

es

. A

ll r

ig

ht

s r

ese

rv

ed

.

REmOTE SENSOR ACCESSORIES

Model no.

Description

S3010W1045

Wall mounted temperature sensor

S3020W1045

Wall mounted temperature sensor with override button and occupancy status LED

Note:
If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Dis-
connecting the sensor(s) in RS terminal will re-activate the internal sensor.

Remote mount temperature sensors inputs use 10K type 2 NTC thermistors.

Features:
• Each sensor can be configured for various averaging combinations
• Optional occupancy led
• Optional override key

Wiring example of single remote room sensor:

VT8600

Series Controller

1xS3020W1000

Remote wiring 1 sensor

S2-1= On, S2-2=On

S3010W1000

Remote wiring 1 sensor

S2-1= On, S2-2=On

SCom

RS

Aux

C

DI

OR

Dip switch setting for 1 sensor

S2-1= On, S2-2=On

SCom

RS

Common

UI 20 - RS

B0 1 - AUX

C (Common)

UI 16

UI 17

ON

1 2

or

Advertising