Vt8600, Vt8600 series installation guide, Series controller – Viconics VT8600 Installation Guide User Manual

Page 9: Remote wiring 3 sensors

Advertising
background image

VT8600 Series

Installation Guide

9

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0435-01

www.viconics.com

February 2015

©

2

01

5 V

ic

onic

s T

ec

hno

lo

gi

es

. A

ll r

ig

ht

s r

ese

rv

ed

.

Wiring examples of 3 remote room sensors for averaging applications:

VT8600

Series Controller

2xS3010W1000 and 1xS3020W1000

Remote wiring 3 sensors

S2-1= Off, S2-2=On

SCom

RS

Aux

C

DI

SCom

RS

SCom

RS

VT8600

Series Controller

1xS3010W1000 and 2xS3020W1000

Remote wiring 3 sensors

S2-1= Off, S2-2=On

SCom

RS

Aux

C

DI

SCom

RS

Aux

C

DI

SCom

RS

Common

UI 20 - RS

B0 1 - AUX

C (Common)

UI 16

UI 17

Common

UI 20 - RS

B0 1 - AUX

C (Common)

UI 16

UI 17

Dip switch setting for 3 sensors

S2-1= Off, S2-2=Off

ON

1 2

Dip switch setting for 3 sensors

S2-1= Off, S2-2=Off

ON

1 2

Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10K

±3%, B25/85°C = 3975K±1.5%)

ºC

ºF

Kohm

ºC

ºF

Kohm

ºC

ºF

Kohm

ºC

ºF

Kohm

ºC

ºF

Kohm

-40 -40 324.3197

-20 -4

94.5149

0

32 32.1910

20 68 12.4601

40

104

5.3467

-35 -31 234.4009

-15 5

71.2430

5

41 25.1119

25 77 10.0000

45

113

4.3881

-30 -22 171.3474

-10 14 54.1988

10

50 19.7390

30 86 8.0694

50

122

3.6202

-25 -13 126.6109

-5

23 41.5956

15

59 15.6286

35 95 6.5499

55

131

3.0016

or

or

Advertising