PARAMETER DETAILS SCREEN 7/9
Configuration Parameters Default Value
Significance and Adjustments
Min CO2
Minimum CO2 Level
Default value:
800 ppm
Minimum CO2 Level required. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 or 100 increments
Max CO2
Maximum CO2 Level
Default value:
1200 ppm
Maximum CO2 Level allowed. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 or 100 increments