Vt8600 series, User interface guide, Appendix a: terminal correspondence – Viconics VT8600 User Interface Guide User Manual
Page 47

VT8600 Series
47
User Interface Guide
© 2
01
4 V
ic
on
ic
s T
ec
hn
ol
og
ie
s. A
ll r
ig
ht
s r
es
er
ve
d
.
Viconics Technologies Inc.
9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00
www.viconics.com
November 2014
APPENDIX A: TERMINAL CORRESPONDENCE
The terminals of an VT8600 are identified differently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000
series and the VT8600 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller
with a VT8600 Room Controller.
VT7000
VT8600
Terminal name
Terminal ID
Terminal name
Terminal ID
Binary Input 1
BI1
Universal Input 16
UI16
Binary Input 2
BI2
Universal Input 17
UI17
Universal Input 3
UI3
Universal Input 19
UI19
Sensor Common
Scom
Terminal 18 Common
COM
Remote Sensor
RS
Universal Input 20
UI20 - RS
Sensor Common
Scom
Terminal 21 Common
COM
Mix/Supply Sensor
MS
Universal Input 22
UI22 - SS