Example 2 with 3 voting master zones only

Voting Zone 1

Voting Zone 2

Voting Zone 3

RTU Control Type

Current heat

demand

Current heat

demand

Current heat

demand

Highest

Average of 3

highest

100% 0% 0%

Heat weight set Heat weight set Heat weight set

100% 100% 100%

Resulting heat
weight to RTU

Resulting heat
weight to RTU

Resulting heat
weight to RTU

100%

0%

0%

100%

33.3%

Current cool

demand

Current cool

demand

Current cool

demand

0% 100% 100%

Cool weight set

Cool weight set

Cool weight set

100% 75% 75%

Resulting cool

weight to RTU

Resulting cool
weight to RTU

Resulting cool

weight to RTU

0%

75%

75%

75%

50%


It can be seen here that the resulting demand used by the RTU controller for the three master voting
zones are different and will result in different heating and cooling action simply based on the RTU
configuration.

If the RTU is set to Control Type = Highest demand, the current action delivered by the RTU
will be heating.

If the RTU is set to Control Type = Average of 3 Highest demand, the current action
delivered by the RTU will be cooling.

Example 3 with 5 voting master zones only

Voting

Zone 1

Voting

Zone 2

Voting

Zone 3

Voting

Zone 4

Voting

Zone 5

RTU Control Type

Current heat

demand

Current heat

demand

Current

heat

demand

Current

heat

demand

Current

heat

demand

Highest Average

of 3

highest

Average

of 5

highest

100% 0%

50%%

50%

0%

Heat weight

set

Heat weight

set

Heat

weight set

Heat

weight set

Heat

weight set

100% 100% 100% 50% 100%

Resulting

heat weight

to RTU

Resulting

heat weight

to RTU

Resulting

heat

weight to

RTU

Resulting

heat

weight to

RTU

Resulting

heat

weight to

RTU

100%

0%

50%

25%

0%

100%

58.3%

35%

Current cool

demand

Current cool

demand

Current

cool

demand

Current

cool

demand

Current

cool

demand

0% 100%

0%

0%

100%

Cool weight

set

Cool weight

set

Cool

weight set

Cool

weight set

Cool

weight set

100% 50% 50% 50% 75%

Resulting

cool weight

to RTU

Resulting

cool weight

to RTU

Resulting

cool

weight to

RTU

Resulting

cool

weight to

RTU

Resulting

cool

weight to

RTU

0%

50%

0%

0%

75%

75%

41.7.3%

25%


It can be seen here that the resulting demand used by the RTU controller for the five master voting
zones are different and will result in different heating action simply based on the RTU configuration.

Please note that the heating or cooling action delivered to the zones is also dependent on heating
and cooling lockout functions based on the outdoor and supply air temperature. Please see the next
section for more information.