5B) Proper Commissioning RTU Controllers


At the

RTU level, care should be applied to insure the following conditions are met:

-

Proper sizing of the RTU heating and cooling capacity to insure it will meet the highest
instantaneous peak loads of the areas deserved by the system.

-

Proper strategy and system layout of the mechanical system architecture.

-

Proper commissioning and verification of the by-pass system. A wrongly configured by-pass
system may cause all the zones in a section of the system unable to get the proper RTU capacity
down to the zones. Even when all of the zones are properly commissioned and all equipment are
properly sized.

-

Proper setup of the configuration parameters: Heating lockout, cooling lockout, control type
strategy, discharge air low and high limits, static pressure sensor range and static pressure
setpoint. All of these need to be properly evaluated and set according to the specifications of the
installation.

-

Proper verification of RTU I/O operation including the RTU on board economizer operation.


5C) Operational System Checklist

It is recommended to keep a checklist of all milestones and configuration settings during start-up. This list
should be kept as a reference with the system when it is fully commissioned. The following is only provided
as a guideline template but can be extremely helpful for servicing issues and questions.

RTU Unit
Manufacturer:

Serial number

Model number:

Year of manufacture

Location:

Date of original installation

Cooling tonnage:

Cooling number of stages:

Heating capacity:

Heating number of stages:

Maximum CFMs:

Total number of zones:

RTU Configuration, critical operational configuration parameters are in bold
RTC MAC

TOccTime

RTC Baud

cal RS

PAN ID

cal

OS

Channel

H

stage

Lockout

C

stage

Pwr del

H Lock

CntrlTyp

C

Lock

Dis HL

2/4event

Dis LL

Aux cont

Anticycl

Prog

rec

Heat cph

Occ CL

Cool cph

Occ HT

Deadband

Unocc

CL

Units

Unocc

HT

Fan del

Sp range

BI 1

Pressure

RTU Local Schedule Settings

2 events

4 events

Occupied

day?

1

st

Occ event

2

nd

Unocc event 3

rd

Occ event

4

th

Unocc event

Monday

Tuesday

Wednesday

Thursday

Friday

Saturday

Sunday

RTC Baud refers to BACnet models only
PAN ID and Channel refers to Wireless models only