RTU Commissioning
RTU mechanical cooling functional verification done

Maximum Delta temperature ( return to supply temp ) for cooling stage #1:

Maximum Delta temperature ( return to supply temp ) for cooling stage #1 & 2:

Economizer cooling functional verification done

Minimum position of economizer properly set?

RTU controller Aux output used to disable minimum position of economizer check ?

RTU heating functional verification done

Maximum Delta temperature ( return to supply temp ) for heating stage #1:

Maximum Delta temperature ( return to supply temp ) for heating stage #1 & 2:

Static pressure transducer input reading fan Off ( should be 0 “WC or 0 PA ):

Maximum static pressure transducer input reading fan On ( all VAV closed ):

Static pressure damper actuator properly rigged and verified?

Important configuration property set?

-

RTC MAC value:

- PAN

ID

- Channel

- CntrlTyp:

- Dis

HL:

- Dis

LL:

- H

Lock:

- C

Lock:

- Sp

range:

- Pressure:

Communication with zones is active? ( Status LED & manual scroll display )

Local time clock set?

Local schedule set?

Local system mode set to Auto? ( System On )

Outdoor air sensor properly connected and displaying value? ( manual scroll display )

Supply air sensor properly connected and displaying value? ( manual scroll display )

Return air sensor properly connected and displaying value? ( manual scroll display )


Zone Number ( ) ,
use MAC address for zone name and repeat for ALL other zones
Location:

Date of original installation

VAV inlet diameter Ǿ in Inches:

Zone vocation and use:

Perimeter zone?

VAV actuator brand:

Internal zone?

VAV actuator model:

Type of reheat if installed:

Capacity of reheat if installed:

Zone Configuration, critical operational configuration parameters are in bold
Zone MAC

Unocc HT

PAN ID

Unocc CL

Channel

St-By

HT

RTC MAC

St-By

CL

Get From

Set Type

MenuScro

TOccTime

C or F

Cal RS

PIR Func

Deadband

Lockout

Heat

max

BI1

Cool min

RehtConf

Min Pos

AO2RA/DA

Max Pos

AO2 OALK

MaxHTPos

BO5 OALK

PIHT Wei

BO5 Time

PICL Wei

BO5 cont

Items in bold items are critical for proper system operation.