Preventive maintenance – Winco ULPSS8B4W/E User Manual

Page 15

Advertising
background image

5

045-00

60706-20

In order to set and test the exercise circuit the

left hand toggle switch on the generator control

panel must be in the ON position.

SETTING THE EXERCISER CIRCUIT

Press and release the

Automatic Generator Exer-

ciser button. After about 8 seconds the exerciser

light flashes 4 times to indicate that the exerciser

circuit has been set. The number of flashes indi-

cates the number of days until the next exercise

period. This 20 minute period will occur at approxi-

mately the same time of the day the button was

pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off. After about 8 seconds the exerciser light

flashes fourteen times to indicate that the exerciser

circuit has be re-enabled.

******************

***** WARNING *****

******************

WITH A TOTAL POWER FAILURE (UTILITY

POWER FAILS AND THE GENERATOR FAILS TO

START AND RUN) THE EXERCISER MUST BE

RESET AFTER THE POWER IS RESTORED.

CLEARING AN “ERROR” CODE

An error codes occurs on the ASCO control board if

the generator set fails to start or there is some other

malfunction. BOTH Transfer Switch lights will be

blinking together. The Automatic Generator Exer-

ciser light will be blinking a number of times then

pause. This number gives the error code reason

from page 8 of the ASCO 65 owner’s manual. To

clear this code press and release the Push to Test

button once. Then troubleshoot the problem accord-

ing to the ASCO 65 owner’s manual.

This completes your installation and unit testing.

ALWAYS leave the system in automatic mode unless

servicing the unit. For automatic operation, the left

hand toggle switch on the generator control panel

must be left in the “ON” position.

PREVENTIVE

MAINTENANCE

Reasonable care in preventive maintenance will

insure high reliability and a long life for the engine

generator set and Automatic Transfer Switch.

*****************

***** WARNING *****

*****************

When performing any type of maintenance on this

equipment make sure the selector switch on the en-

gine generator is in the off position. If you are work-

ing in the Automatic Transfer Switch, confirm with a

reliable meter that all power has been disconnected.

AUTOMATIC TRANSFER SWITCH

Clean and inspect the switch once a year. de-ener-

gize all power sources, both line and engine genera-

tor set, then brush and vacuum away any excessive

dust or dirty accumulation. You can at this time with

the contactor de-energized remove the contactor

covers and check the contacts. Make sure contacts

are clean and not burned or pitted.

ENGINE GENERATOR SET

Service the engine in accordance with the engine

manufacturers manual provided with your new

equipment. Routinely remove debris and dirt from

around the inside generator enclosure. Insure that

the air intakes are free from leaves and other debris

at all times.

Clean and inspect battery terminals a least twice a

year. Check the battery water level at least twice a

year also.

Other than keeping the generator clean and free of

debris there is no other routine or preventative main-

tenance required, as long as the generator is run

biweekly to keep it dry and in good working order.

COLD WEATHER OPERATION

Extreme cold weather operation requires special

considerations. Higher CCA batteries are required

for cold weather starting, 650 CCA or larger are rec-

ommended. In addition you should consider install-

ing an oil heater kit and a battery warmer for reliable

starting during cold weather.