FUNCTIONS

DSE 7310 Series Control Modules perform the following

protection and metering functions:

Generator Protection and Metering

Generator protection includes over voltage, under voltage,

under frequency, over frequency and overload protection. Each

generator protection function has an adjustable pickup and time

delay setting. Metered generator parameters include voltage,

current, real power (watts), power factor (PF)

Engine Protection and Metering

Engine protection features include oil pressure and coolant

temperature monitoring, over crank protection, ECU specific

protection elements, and diagnostic reporting.

Metered engine parameters include, oil pressure, coolant

temperature, battery voltage, speed, engine load, coolant level

(from ECU), ECU specific parameters, and run-time statistics.

** NOTICE **

These units will automatically transfer if a power outage occurs

while running in an exercise mode.

SPECIFICATIONS

LP RATING

MODEL

WATTS VOLTS

AMP

HZ

PH RPM

PSS60-3

56,000 10/40

33*

60

1

1800

PSS60-4

60,000 10/08

08**

60

3

1800

PSS60-17 60,000 10/40

180**

60

3

1800

PSS60-18 60,000 77/480

90**

60

3

1800

PSS90-3

80,000 10/40

333*

60

1

1800

PSS90-4

80,000 10/08

78**

60

3

1800

PSS90-17 80,000 10/40

40**

60

3

1800

PSS90-18 80,000 77/480

10**

60

3

1800

NG RATING

MODEL

WATTS VOLTS

AMP

HZ

PH RPM

PSS60-3

55,000 10/40

9*

60

1

1800

PSS60-4

58,000 10/08

01**

60

3

1800

PSS60-17 58,000 10/40

174**

60

3

1800

PSS60-18 58,000 77/480

87**

60

3

1800

PSS90-3

90,000 10/40

375*

60

1

1800

PSS90-4

90,000 10/08

31**

60

3

1800

PSS90-17 90,000 10/40

70**

60

3

1800

PSS90-18 90,000 77/480

135**

60

3

1800

*Unity Power Factor - Derate 3.5% per 1000 feet elevation above

sea level.

**Power Factor .8 - Derate 3.5% per 1000 feet elevation above

sea level.

FUEL CONSUMPTION

NG

LP VAPOR

(1,000 BTU/CU FT) (2,520 BTU/CU FT)

MODEL CF/

HR

BTU/HR

#/HR GAL/

HR

CF/

HR

BTU/HR

PSS60

799

799,000

39.4

9.9

334 850,964

PSS90

130 1,30,000 5.6

1.4

446 1,149,00

L.P. TANK SIZING

Minimum required L.P. Tank size for L.P. Vapor withdrawal

operating at various outside temperatures given in degrees

Fahrenheit (Celsius)

TANK TEMPERATURE

MODEL 60 F(16 C) 30 F(0 C) 0 F(-18 C) -20 F(-29 C)
PSS60

500 Gal

1000 Gal 000 Gal*

5000 Gal*

PSS90

500 Gal

1000 Gal 000 Gal*

5000 Gal*

*Recommend liquid withdrawal at these temperatures.

ENGINE SPECIFICATIONS:

** NOTICE **

Regarding Engines - This manual covers the generator portion

of these units. See the separate engine instruction manual

for engine-related problems, detailed engine information and

engine warranty. Refer to engine operating and maintenance

instructions

** CAUTION **

EQUIPMENT DAMAGE - Be sure to check the engine oil level

frequently as specified in the engine manual.

The engine manufacturer has established an excellent worldwide

engine service organization; engine service is available from a

nearby authorized dealer or distributor. Go to the WINCO web

site for a list of engine dealers. (http://www.wincogen.com/

Engine_Support/ )

The rated power of each engine-generator is limited by the

temperature, altitude and all other ambient conditions specified

by the engine manufacturer. Engine power will decrease 3-1/%

for each 1000 ft. above sea level, and will decrease an additional

1% for each 10

o

Fahrenheit above 60

o

Fahrenheit. Units should

not be operated in ambient temperature greater than 104

o

F.

Advertising
This manual is related to the following products: