Control features (continued), Source availability signal contacts, Programmable engine–generator exerciser – Winco ASCO 300 G Design 1000-3000 Amp User Manual

Page 14: S1 dip switch settings in group 1 controller, S2 dip switch settings in group 1 controller

Advertising
background image

CONTROL FEATURES (continued)

5--2

Optional Accessory 11BG – SOURCE AVAILABILITY SIGNAL

& PROGRAMMABLE ENGINE EXERCISER MODULE

2–line

display

3 buttons

connections

for power source

availability

signal contacts

located on inside of

door behind operator

interface on engine

exerciser module

Source Availability Contacts

2 amps @ 30 VDC, resistive

0.5 amp @ 125 VAC, resistive

contacts shown de–energized

Figure 5–2. Accessory 11BG module (mounted behind operator

interface and connected to the controller) includes source

availability signal contacts and a programmable engine exerciser.

Figure 5–3. Source availability

signal contacts.

Source Availability Signal Contacts

The module provides one Form C contact each for the
normal and emergency sources signal the acceptability of
the source as sensed by the controller. The signal contacts
operate in conjunction with the Source Available lights on

the operator interface. Field wiring terminals are
provided as shown in Figure 5–3 and the wiring diagram.

Contact ratings:

2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive

Programmable Engine–Generator Exerciser

The module includes a programmable engine exerciser
that provides for weekly or biweekly operation. This
optional exercise timer may have to be turned on
(enabled) by setting the S1 DIP switch actuator 7 to OFF
(left position), and S2 DIP switch actuator 5 to OFF (left
position).
A backup battery in the controller (see page 4–2 and page
5–3) must be turned on to maintain the settings and to
allow programming with the normal and emergency
power turned off (page 5–1).

The programmable engine exerciser incorporates a 7–day
or 14–day time base. Proper controller settings must be
made to determine whether or not the test will be done
with or without load transfer (S1 DIP switch actuator 8).

See next page for instructions on setting the timer.

S1 DIP Switch Settings

in Group 1 Controller

Programmable

Exerciser

Function

ACTUATORS 7 & 8

OFF ON

Enabled &

Exercise

without Load

Actuator 7 OFF

Actuator 8 OFF

7

EXER ACTV

8

LOAD

Enabled &

Exercise

with Load

Actuator 7 OFF

Actuator 8 ON

7

8

EXER ACTV

LOAD

S2 DIP Switch Settings

in Group 1 Controller

Programmable

Exerciser

Function

ACTUATOR 5

OFF ON

Enabled

Actuator 5 OFF

5

EXT EXER

Disabled

Actuator 5 ON

5

EXT EXER

Shaded DIP switches are standard factory settings.