The Device Configurator Screen for Series 300 ATSs shows the Group 1 controller
configuration settings (right side) and the Connectivity Module (server) configuration
settings (left side) for the selected ATS.

Group 1 Controller Configuration (right side)
Enter or change the ATS Name (8 char. max.) and the ATS Location (20 char. max.). Press
the Update button when finished to save the Group 1 controller configuration changes.

Connectivity Module (server) Configuration (left side)
Several configuration settings must be set appropriately as described below. Press the Update
Server
button when finished to save configuration changes.

Device Configurator Screen without Power Manager

Device Configurator Screen with Power Manager

ATS
Location

ATS
Name

Serial Port Speed 9600

Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
1024-65535, but do not use
ports 14000-14009 or 30718)

Press Update button when finished to
save the configuration changes. Do this
before you press Update Server button.

After Controller or PM has been
updated, press Update Server button
to save the configuration changes.

Flow Control No flow control

Interface Mode RS422/485-4Wire

ATS
Location

ATS
Name

Serial Port Speed 9600

Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
1024-65535, but do not use
ports 14000-14009 or 30718)

Press Update button when finished to
save the configuration changes. Do this
before you press Update Server button.

After Controller or PM has been
updated, press Update Server button
to save the configuration changes.

Flow Control No flow control

Interface Mode RS422/485-4Wire

Press to configure Power Manager.

Press to configure Group 1 Controller.