4-1 ASCO 940/962 ATSs

Connectivity Module

Device Configurator Screen for ASCO 940/962 ATSs

The Device Configurator Screen for ASCO 940/962 ATSs shows the Group 7A controller configuration
settings (right side) and the Connectivity Module (server) configuration settings (left) for the selected ATS.

Group 7A Controller Configuration (right side)
Enter or change the ATS Name (18 char. max.) and ATS Nominal Voltage (must be entered to get correct
reading). Press the Update button when finished to save the Group 7A controller configuration changes.

Connectivity Module (server) Configuration (left side)
Several configuration settings must be set appropriately as described below. Press the Update Server button
when finished to save configuration changes.

Device Configurator Screen without Power Manager

Device Configurator Screen with Power Manager

Nom. Voltage

ATS Name

Serial Port Speed 9600

Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
10024-65535, but do not use
ports 1400-14009 or 30718)

Press Update button
when finished to save
the configuration

Press Update Server button
when finished to save the
configuration changes.

Flow Control No flow control

Interface Mode RS422/485-4Wire

Nom. Voltage

ATS Name

Serial Port Speed 9600

Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
10024-65535, but do not use
ports 1400-14009 or 30718)

Press Update button
when finished to save
the configuration

Press Update Server button
when finished to save the
configuration changes.

Flow Control No flow control

Interface Mode RS422/485-4Wire