Danger, Troubleshooting – Winco ZTX-RM Series 40-400 Amps User Manual

Page 14

Advertising
background image

12

GE Zenith Controls

ZTX-RM Operation and Maintenance Manual (62R-2000)

Troubleshooting

Symptom

Possible Cause

Corrective Action

Generator will not start

P timer has not lapsed

See factory settings on Page 5

Generator control switch not in Auto

Refer to generator instruction manual

Engine Start contact not wired
to generator

See Figure 3, Page 4

Starter battery is dead

Refer to generator instruction manual

No fuel

Refer to generator instruction manual

Transfer switch does not
transfer to Utility

T timer has not lapsed

See factory settings on Page 5

Exercise in progress

See Page 8

Utility breaker open or tripped

Clear fault and reset

Utility voltage out of range

Wait for utility to return to acceptable
level. See factory settings on Page 5.

Control harness unplugged

With all power disconnected,
reconnect harness

Transfer switch does not
transfer to Generator

W timer has not lapsed

See factory settings on Page 5

Generator breaker open or tripped

Refer to generator instruction manual

Generator voltage out of range

Refer to generator instruction manual

Control harness unplugged

With all power disconnected,
reconnect harness

Generator will not stop

U timer has not lapsed

See factory settings on Page 5

Exercise in progress

See page 8

Engine control switch in run position

Refer to generator instruction manual

All LEDs off

Keypad cable unplugged

With all power disconnected,
reconnect harness

Sources unavailable and/or source
breakers tripped or open

Clear fault and reset breakers and/or
check source availability

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, manual operation or removal of transfer switch or any of its components.

Connecting Engine Start may cause Generator to start. Before connecting, turn Generator OFF.

Service must be performed by qualified personnel.