GE Zenith Controls

3

ZTX-RM Operation and Maintenance Manual (62R-2000)

GENERATOR

TERMINALS

N

BR

UTILITY

TERMINALS

LOAD

TERMINALS

T1

T2

T3

N1

N3

E1

E3

E2

N2

T = Load

N = Utility

E = Generator

CONTROLLER

ENGINE
START

OPTIONAL A4 CONTACT

OPERATES WHEN IN
UTILITY POSITION

OPTIONAL A3 CONTACT

OPERATES WHEN IN
GENERATOR POSITION

JP

Exerciser

OPTIONAL ENGINE CONTROLS
OR AIR CONDITION DISCONNECT
OR 3 PHASE BOARD

3 AND 4 POLE ONLY

SWITCH
POSITION
INDICATOR

Install

load

cables

first.

Tip!

Table 2

Screw Type Terminals for External Power Connections

Switch Size

(Amps)

40

80

100

150

Utility, Generator and Load Terminals

1

#8 to 3/0 AWG

Cable Per Pole

Range of Wire Sizes

1

#8 to 3/0 AWG

1

#8 to 3/0 AWG

1

#8 to 3/0 AWG

Fully Rated Neutral Bar (When Required)

3

#8 to 1/0 AWG

No. of Cables

Range of Wire Sizes

3

#8 to 1/0 AWG

3

#8 to 1/0 AWG

3

#8 AWG to 300 MCM

200, 225, 250*

300, 400

1

#6 AWG to 250 MCM

1

#4 AWG to 600 MCM

3

#6 AWG to 300 MCM

3

#4 AWG to 300 MCM

* IEC Rating Only

Installation

(cont’d)

Figure 2 - Power Panel

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, manual operation or removal of transfer switch or any of its components.

Connecting Engine Start may cause Generator to start. Before connecting, turn Generator OFF.

Installation must be performed by a licensed electrician and in accordance

with the National Electric Code and all local electrical codes.