A

condenser

selection

that

is

heavily

loaded

requires

the

compressor

to

operate

at

a

higher

condensing

temperature,

results

in

higher

compressor

motor

brake

horsepower

and

operat­

ing cost.

For

a

given

compressor-condenser

combina­

tion,

the

selection

of

a

condensing

temperature

may depend on the ratio between power costs and
water costs, on the quantity of water available, on
the

condensing

temperature

required

to

achieve

compressor

capacity,

or

possibly

the

require­

ment to remain within the allowable loading on a
given motor size.

Table 25 - Condenser Water Circuiting

WATER CIRCUITING

ARRANGEMENTS

CONDENSER SIZE

CONDENSER

CHARACTERISTICS

NORMAL USE

Double Circuit

5F20, 5F30

High Water Quantity

Low Pressure Drop

4 Passes

5F40, 5F60

Cooling Tower

3 Passes

All 09RH

Single Circuit

5F20, 5F30

Low Water Quantity
High Pressure Drop

8

Passes

5F40, 5F60

City or Well Water

6

Passes

All 09RH