Carrier 28QX User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Fig. 7 — Typical Collector Mounting Frame

MOUNT THE COLLECTORS on completed frame
or sleepers. Lasten in place with four mounting
clips supplied with each collector. Use 2 clips on
each end of the collector. See Fig. 8. Each clip has

a .437-in. diameter hole to accept a field supplied
mounting screw. Use a level to align the collectors

exactly parallel to the horizontal plane, Fig. 9.

NOTE: There is no fixed top or bottom to a
collector. It can be installed either way,
although it may be preferable to install so
nameplate can be read.

NOTE: Supply and return piping must be sloped

Fig. 9 — Collector Panel Leveling

MAKE PIPING CONNECTIONS - Attach supply
and return piping headers and lines to collectors.
Piping supply line size is specified by Solar CLIC.

Return line is 2-1/8 in. O.D. on all systems. See
Fig. 10. The headers can be completely pre­
fabricated.

Determine

distance

between

the

collector inlet connections and outlet connections
(35-in. if panels are butted up to each other). Make
headers with regularly spaced T-sections to mate
with the inlet and outlet of the collector array.

Acquire two 3/4-in. MPT to 3/4-in. sweat

copper fittings for each collector. To each fitting,
solder (95-5) a 3/4-in. copper pipe stub of appro­
priate length to maintain a minimum vertical

1/4-in. slope/ft of header. It might be necessary to

bend the copper stubs to maintain this vertical
slope. Thread the fittings with copper stub

attached into the collectors and solder the headers
onto the stubs (Fig. 10). Solder the supply and
return lines in place. Install a tee with a pressure
relief valve between the leaving header and 2-1/8
in. return pipe. Use an ASME approved pressure
relief device with a 50 psig set point and a manual
release lever. (See Leak Testing below.)

If it is necessary for return and supply pipes to

penetrate the roof, install a pitch pocket to seal the
opening.

Install the Collector Sensor on an interior collector
panel after headers have been soldered in place.

Sensor location and method of attachment is
described on pg 15.

LEAK TEST THE COLLECTOR ARRAY ^ Using

city or well water with a minimum pressure of 30
psig, leak test the collectors and piping as follows;

;a. Soft solder (50-50) a temporary cap or end of

2-1 /8 in. collector return line.

b. Attach water supply line to collector supply

pipe.

c.

Fill collector array with water using release

lever on pressure relief valve (Fig. 10) to bleed
air from collector system. If relief valve does

not have a manual release lever, temporarily
replace the relief valve with an air bleed valve.

d. Leave water pressure on to system and check

collectors and piping for leaks per local codes.

e.

If leaks occur, drain water from system by

removing water pressure source. Repair leak
and repeat steps b, c, d and e.

f.

Using a tubing cutter, remove temporary cap

from 2-1/8 in. return line. (This liiie will be
filled with water.)

10

Advertising