THERMOSTAT

Factory Wiring

--------- Field Wiring

Fig. 8 — Control Wiring Connections

Route thermostat cable or equivalent single leads

of colored wire from subbase terminals through con­
nector on unit to low-voltage connections as shown
in Fig. 8.
NOTE: For wire runs up to 50ft, use no. 18 AWG
insulated wire (35 C mininum). For 50 to 75 ft, use
no. 16 AWG insulated wire (35 C minimum).

Pass the control wires through the hole provided

in the corner post; then feed wires through the race­
way built into the corner post to the 24-v barrier
located on the left side of the control box.

HEAT ANTICIPATOR SETTINGS — Set heat

anticipator settings at 1.20 for 460-voIt units and

1.00 for 208/ 230-volt units. Settings may be changed

slightly to provide a greater degree of comfort for a
particular installation.

Step 8 — Make Outdoor Air Inlet Adjustments
and Install Outdoor Air Hood

OPTIONAL OUTDOOR AIR DAMPER

48HDT,LDT004,005,006 and HD007 — Optional

outdoor air damper is shipped with hood broken
down inside of unit. See Fig. 9.

Assembly

1. Remove filter access panel.

2. Remove sheet metal parts from filter area.
3. Using screws provided, a.s.semble sides to the

inside of the hood. See Fig. 9.

4. Discard baffle.

5. Install damper blade by inserting threaded pins

through hole in side plates.

6. Use wing nuts provided to hold blade in place.
7. Install outdoor air hood assembly, using screws

provided.

8. Install outdoor air inlet screen and screen

retainer.

9. Replace access panel.

Fig. 9 — Outdoor Air Damper and Hood

Installation and Details

(004,005,006.007 Units)

Fig. 10 — Access Panel Location

(008 Units)

lO. Loosen wing nut on side plate to adjust blade.

Adjust damper blade to desired setting for out­

side air intake.

48HD,LD/ HDD,LDD008 — Optional outdoor air
damper is shipped with hood broken down in unit

filter section. See Fig. lO.
Assembly

1. Remove protective cover from unit. See Fig. lO.

2. Remove upper filter aecess panel (save screws).

See Fig. lO.

3. Remove hood parts from unit evaporator fan

and filter area. Assemble hood top and side
plates as shown in Fig. 11. Do

n ot attach h ood

to u n it at th is tim e.

4. Adjust outdoor air damper blade to desired

setting for outside air intake by releasing linkage
rod setscrew and adjusting linkage rod. See

Fig. 12. Secure damper blade in desired position
with setscrew.

5. Remove screws holding manual outdoor air

damper to unit. See Fig. 13.