06D,07D
INSTALLATION
Carrier
m
T T
TURN CLOCKWISE TO INCREASE
ACTUATING PRESSURE}
COUNTERCLOCKWISE TO DECREASE
LOADING POINT MAY BE SET
ANYWHERE FROM 0-PSIG
TO 85-PSIG MAX.
(A) UNLOADED OPERATION
DIFFERENTIAL ADJUSTMENT
REMOVE SEALING CAP AND
TURN CLOCKWISE TO INCREASE
DIFFERENTIAL j
COUNTERCLOCKWISE TO
DECREASE.
ONE TURN = 2-PSI
REPLACE AND TIGHTEN
SEALING CAP.
DIFFERENTIAL MAY BE
ADJUSTED FROM
6-PSI MIN. TO
22-PSI MAX.
(B) LOADED OPERATION
Fig. 25 - Pressure Actuated Capacity Control System - 06D Compressors
30