ELECTRICAL DATA (Cont)

ELECTRICAL DATA (60-Hz)

V/PH

VOLTAGE

RANGE

UNIT

COMPR*

IFM OFM

WSA ICF

FU

FLA

LRA

FLA (ea)

208/3

220-180

79.6

152

100

27.60

1 10

10.6

3.2

230/3

254-198

70 0

137

90

23.80

100

9.2

3 2

460/3

506-414

33 9

69

45

11 85

50

4.6

1 2

IFM

— Indoor Fan Motor

LRA

— Locked Rotor Amps

OFM

— Outdoor Fan Motor

WSA

— Wire Sizing Amps per NEC equals 1 25

X

FLA of the largest

motor

plus

the

sum

of

the

FLA

of

all

other

motors

in

the unit.

*Unit has two compressor motors; values are for each.

FLA

— Full Load Amps

FU

— Fuse (max allowable amps)

ICF

—Max Instantaneous Current Flow during start-up is the sum of

compressor LRA plus the FLA of all other motors in the unit

TYPICAL PIPING AND WIRING

ROOFTOP INSTALLATION WITH SEPARATE SUPPLY AND RETURN DUCTWORK

APPLICATION

ADDITIONAL UNIT AI R FLOW ARRANGEMENTS

CONCENTRIC DUCTING THRU THE BOTTOM

THRU T

he

side

[^AIRFLOW

note

; Accessory economizer cannot be used with this air flow arrangement.