APPLICATION (Coni)

LOW OUTDOOR TEMPERATURE COOLING OPERATION

It

is

not

necessary

to

use

the

refrigeration

system

for

cooling

when

the

outdoor

air

temperature

is

below

60

F.

The

use

of

outdoor

air

will

handle

the

cooling

load.

This

is

a

more

economical

method of cooling in cold weather

One

condenser

fan

motor

is

cycled

off

when

the

outdoor

air

temp drops to 55 F. This allows operation down to 35 F outdoor

temperature

The

other

condenser

fan

motor

is

suitable

for

use

with

the

32LM

MotormasterTM

Head

Pressure

Control

at

outdoor

temperatures

below

35

F

(see

Accessories).

Operation

with

this

control

requires

winter

start

provisions

(low

pressure

switch

recalibration):

and

may

require

field-fabricated

condenser

air

baffles.

CONTROLS (Protective Devices)

Limit Switches

shut off gas supply if excessive air temperatures

should

develop;

limit

discharge

air

temperature

to

175

F

when

unit

is used for heating.

Current Overloads with Automatic Reset

are current sensitive

and

temperature

compensated;

will

open

the

control

circuit

if

compressor current is excessive.

Internal Thermostat with Automatic Reset

Is embedded in

compressor

windings;

de-energizes

the

control

circuit

if

extreme

temperatures

should

develop

due

to

excessive

suction

gas

tempera­

ture or motor overloading

High Pressure Relief Device

protects unit from excessive com­

pressor discharge pressures and prevents overheating.

• Circuit Breaker

provides short circuit protection for controls.

Low Pressurestat with Automatic Reset

de-energizes the control

circuit

if

refrigerant

pressure

drops

below

setting;

provides

pro­

tection from loss of refrigerant charge.

Inherent Fan Motor Protection with Automatic Reset

opens

power

circuit

if

temperatures

or

current

become

excessive

on

3-phase motors (single-phase motors are temperature sensitive only).

Fusible Plug

located

on

the

accumulator,

protects

against

excessive pressures or temperatures in the refrigerant system.

Centrifugal Switch

located

in

the

induced

air

fan

motor

will

de-energize the gas valve in case of combustion air failure.

GUIDE SPECIFICATIONS

Unit

shall

be

of

the

single-package

type,

combination

air-to-air

cooling and gas-fired heating.

Total Net Cooling Capacity

of the system shall be 124,000 Btuh

or

greater,

and

sensible

capacity

shall

be

94,900

Btuh

or

greater,

at

conditions

of:

4500

cfm

evaporator

air

entering

unit

at

67

F

wet-bulb,

80

F

dry-bulb

and

condenser

entering

air

temperature

of

95 F dry-bulb Compressor power input shall not exceed 15.5 kw.

Heating Capacity

of the system shall be 206,000 Btuh or greater,

with gas input of 275,000 Btuh

Casing

shall

be

constructed

of

galvanneal

steel,

bonderized

and

coated with baked enamel

Compressor

The

unit

shall

contain

two

hermetic

compressors

with

suitable

vibration

isolators.

Crankcase

heaters

shall

be

supplied

with the unit

Coils

shall

be

constructed

with

aluminum

plate

fins

mechanically

bonded to copper tubes

Fans and Motors

-

The

indoor

fan

shall

be

of

the

forward-

curved centrifugal type, belt driven by a 3 hp motor The condenser

section

shall

have

two

propeller

fans,

each

directly

driven

by

a

1/2

hp motor.

Heat Exchanger

shall

be

constructed

of

corrosion

resistant

aluminized

steel.

Burners

shall

be

of

the

Bunsen

(aerated)

slotted

port type: readily accessible, and covered by a 10-year warranty.

Safety Controls

Cooling

section

shall

be

protected

by: fusible

plug,

low

pressurestat,

compressor

motor

overloads,

and

a

timing

device

which

will

prohibit

the

compressor

motor

from

being

subjected to starting current more than once every five minutes.

Heating Controls

shall

consist

of

an

automatic

gas

valve,

pilot,

automatic ignition system, limit switches and a centrifugal switch.

Dimensions

— The unit casing shall have width of not more than

65 in., length of not more than 87 in , and height of not more than

42 inches

Accessories

Roof

Curb,

Modulating

Outdoor

Air

Control,

Remote

Control

Center,

Two-Stage

Heat-Cool

Automatic

Change­

over

Thermostat,

Relief

Damper,

LP

Conversion

Kit,

and

32LM

MotormasterTM Head Pressure Control.

Manufacturer reserves the right to change any product specifications without notice.

C A R R I E R A I R C O N D I T I O N I N G C O M P A N Y • S Y R A C U S E , N E W Y O R K

Tab 6

Form48DD-1P New

Printed in U.S.A.

2-70

Codes B and MS