Carrier

«>

Hermetic Reciprocating
Compressors
40 thru 160 Tons

зон R

160

30HR,HS040, 050,060

30HR,HS070thru 160

DESCRIPTION

These modern multiple-compressor liquid chilling pack­

ages offer all the conveniences and economy of packaged

design, for use in chilled water air-conditioning systems and
various types of process cooling applications. Every

machine is completely factory engineered and assembled to

ensure a perfectly balanced refrigeration system. All com­

ponents are matched to perform with high efficiency and

low power consumption. Only external water and electrical

connections must be completed to make the water-cooled

unit operational. Condenserless models require, in addition,

only refrigerant line connections to the remote condenser.

The water-cooled model (30HR) is a complete one-

package system with two condensers having built-in sub­
coolers, and a direct expansion cooler with two refrigerant*,

circuits, one for each condenser.

Model 30HS is a condenserless 30HR, designed for use

with remote water-cooled, air-cooled or evaporative type

condensers Includes all features of the 30HR.

Multiple serviceable compressors are mounted on spring

vibration isolators to minimize sound and vibration trans­

mission to the unit frame and the building structure.

Hot-gas mufflers dampen compressor gas pulsations, giving

smooth, quiet operation.

Each refrigerant circuit includes a thermal expansion

valve, a liquid line solenoid valve, a filter-drier and

combination liquid line sight glass and moisture indicator.

Compact construction allows passage thru 36-inch door­

way. Little floor space required for installation.

FEATURES

•

Low Inrush and Running Current because of sequential

starting and stopping

Multiple Compressors*.

•

Easy to Service bolted-hermetic compressors.

•

Wide Range of Distribution Voltages (208 v to 600 v)

allowed by

Carrier Voltage Standards*.

•

Protection against Single-Phasing of compressor motors,

assured by manual reset,

magnetic-trip circuit breakers.

•

Internal Motor Protection against overheating, provided

by

quick-sensing elements

embedded in motor windings.

•

Optimum Control of Chilled Water Temperature for

closer

Capacity

Control

provided

by

Multiple-Step

Controller.

•

Balanced Wear on Compressors assured by

manual

transfer switch,

which changes the lead compressor in the

starting sequence.

•

Increased System Capacity, without raising horsepower

requirements, afforded by

refrigerant subcooling.

•

Protection against Refrigerant Migration and Oil Dilution

provided by

compressor crankcase heaters,

which are on

during compressor off cycle.

•

Reduced Power Costs because of partial load operation

at higher suction temperatures made possible by

two

separate refrigerant circuits.

©Carrier Corporation 1969

^Single feature sheet available

Form 30HR,HS-5P