TROUBLESHOOTING

SYMPTOM AND

PROBABLE CAUSE

PROBABLE REMEDY

COMPRESSOR DOES NOT RUN
Opening in Power Circuit
1 Control off
2. Blown fuse
3 Defective wiring
4 Defective service cord
5 Loose electrical connections
6 Faulty switches, thermostat, or fan

1 Reset control button

2 Replace fuse
3 Replace wiring
4 Replace service cord

5 Tighten connections
6 Replace defective component

Compressor Power Supply Open

1 Loose leads at compressor terminals

2 Defective motor overload switch
3 Defective capacitor

4. Open compressor windings

5. Seized compressor

1 Tighten leads

2 Replace switch
3 Replace capacitor
4 Replace compressor

5 Replace

compressor

COMPRESSOR RUNS BUT CYCLES

Fan Operating Erratically
1 Loose lead at fan motor
2. Defective or burned out motor
3 Outdoor air restricted or recirculating

4 Overcharge or noncondensables in system

5 Restricted discharge line
6 Defective motor overload switch

1 Tighten lead

2 Repair or replace motor
3 Check for dirty filter, proper clearances around unit —

remove any obstructions

4 Recover refrigerant, evacuate and recharge system according to

nameplate specifications

5. Check for obstruction in line, replace tubing if required

6 Replace switch

Cycles on Compressor Overload

1 Defective run capacitor

2 Defective compressor bearings or valves
3 Greatly restricted indoor air (Iced evaporator coil)
4 Low refrigerant charge
5 Evaporator capillary restricted
6 Liquid line restricted

7. Compressor hot

8 Weak or inconsistent iine power

1 Replace capacitor

2 Replace compressor
3 Defrost evaporator coil

4 Add charge according to approved method
5 Replace capillary

6

Replace strainer

7 Verify refrigerant charge
8 Check line voltage at time of compressor start-up

INSUFFICIENT COOLING
Cooling Air Not Adequate

1 Dirty filter or coil

2. Iced evaporator coil (slightly low refrigerant charge)
3 Defective fan motor

1 Clean as required

2 Recharge
3 Replace fan motor

Condenser Air Not Adequate

1 Condenser air restricted

2 Dirty coil
3 Defective fan motor

1 Check for obstructions and dirty filter Remedy as required

2 Clean coil
3 Replace fan motor

Unit Undersized

Re-evaluate unit for proper capacity

Air Leakage

Check caulking around sleeve Repair if necessary

Capillary Restricted

Replace capillary

Compressor Flooding
1 Unit overcharged

2 Low evaporator airflow

1 Recover refrigerant, evacuate and recharge system according to

nameplate specifications

2 Clean filter and/or evaporator coil

AIR SWEEP NOT WORKING
1 Cam disengaged from lever
2 Air sweep motor failure

1 Activate motor and allow cam to re-engage

2 Replace motor

MESSAGE DISPLAY CODES

d
CP

PF

01

Unit in Dehumidification mode

Unit in Compressor Protection mode Allow 2 minutes for restart

Power failure
Room air thermistor failure