Charge with refrigerant, Vapor charging method, 30hh,hj – Carrier 30HH User Manual

Page 20: Installation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

30HH,HJ

INSTALLATION

TYPE LIQUID SHUT-OFF VALVE CHARGE

USING VAPOR METHOD

Fig. 26 - 30HH Condenser Liquid Line Shut-Off Valves

5. Check chiller leaving temperature to see

that it remains well above freezing.

6. Check compressor oil level ("Oil Charge”).

CHARGE WITH REFRIGERANT

Each system in the 30HH and HJ units must be
charged individually.

IMPORTANT:

30HH015,020

units

are

fully charged at factory.

Charge early models of the 30HH015 to 030 units
using the vapor charging method.

Charge later models of the 30HH units using
liquid charging method. A redesign of the con­
denser

liquid

shut-off

valve

makes

it

possible

to charge liquid refrigerant thru the gage port

directly into the chiller, when the valve is in the
front

seated

position.

Check

Fig.

26

showing

both valves to determine the method of charging
to be used.

CAUTION:

When

charging

the

units,

circulate

water

thru

the

condenser

(30HH) and chiller (30HH and HJ) at all
times to prevent freezing. Freezing of
equipment

with

resulting

damage

is

considered

abuse

and

not

covered

by

the Carrier Warranty.

Vapor Charging Method

Vapor charge the units thru compressor suction
shut-off valves as follows:

1. Backseat the suction shut-off valve.

2.

Connect a refrigerant cylinder loosely to the

gage connection of the suction shut-off valve.
The charging line should contain a drier.

3.

Purge the charging line and tighten the con­

nections.

4.

Turn the stem of the suction shut-off valve

clockwise a couple of turns.

5.

Stand the cylinder upright so that only gas is

charged into the system. Crack valve on the

charging

cylinder

and

break

vacuum

(30HJ

units) with refrigerant vapor. Open the valve
of the charging cylinder and start the com­
pressor.

(See

”Start-Up

Procedures.”)

Al­

low

the

compressor

to

cycle

on

the

low-

pressure

cut-out

until

the

refrigerant

charge

builds

up

sufficiently

to

permit

continuous

compressor operation.

As

the

cylinder

is

discharged,

its

pressure

will eventually drop to the same level as suc­
tion

pressure.

The

remaining

refrigerant

can

be drawn from the cylinder by front seating
the suction shut-off valve and pulling a vac­
uum on the cylinder.

6.

Check

the

refrigerant

charge

frequently

at

the

moisture

liquid-indicator.

A

steady

flow

of liquid refrigerant will indicate a sufficient

charge.

7.

When the unit is sufficiently charged, close

the cylinder valve, backseat the suction shut­
off valve, and remove the charging apparatus.

Replace the plug in the suction shut-off valve.

20

Advertising