Evaporator Blower Adjustrnent

— Blower motor

pulleys are factory set for speed shown in Table 1.
To change blower speed:

1. Shut off unit power supply.

2 Loosen belt by loosening blower motor mount­

ing plate nuts.

3 Loosen movable pulley flange setscrew (see

Fig. 17).

4

Screw movable flange toward fixed flange to

increase speed and away from fixed flange to
decrease speed. Increasing blower speed in­
creases load on motor. Do not exceed maximum
speed specified in Table 1.

See Table 6 for air quantity limits.

5. Set movable flange at nearest key way of pulley

hub and tighten setscrew. (See Table 1 for speed
change for each full turn of pulley flange.)
To align blower and motor pulleys, loosen

blower pulley setscrews and slide blower pulley
along blower shaft. Make angular alignment by
loosening motor from mounting plate.

MOVABLE

a.ANG£S

STRAIGHT EDGE

MOST BE

4WRAU£L

\VWTH8ELT f\

IsETSCREWsj^^'^l

SETSCREVVS

'ПХЕО FLANGES^

Si№LE-GROOve TVfO-GROOVE

MOTOR a FAR SHAFTS
MUST BE PARALLEL

Fig. 17 — Indoor Blower Pulley Adjustment

To Adjust Belt Tension

— Loosen blower motor

pivot bolts. Move motor mounting plate up or
down for proper belt tension (1/2-in. deflection
with one finger) and tighten pivot bolts. Adjust
lock bolt and nut on mounting plate to secure in
fixed position.

Outdoor Air Fan Adjustment

(Fig. 18) Shut off

unit power supply. Remove fan top grille assembly

and loosen fan hub screws. Adjust fan height on
unit using a straight edge placed across the fan
orifice. Tighten setscrews and replace rubber hub­
cap to prevent hub from rusting to motor shaft.
Fill hub recess with permagum if rubber hubcap is
missing.

Economizer Adjustment

1. Set enthalpy control at its highest setting. If

outdoor temperature is above 70 F, perform
the following; install jumper between enthalpy
control terminals 1 and 2 (red and yellow wires).

Fig. 18 — Outdoor Air Fan Adjustment

2. Set system selector switch at COOL and set

cooling selector lever at lowest setting. (Cooling
mode may be simulated by removing thermostat
wires from terminals Y1 and Y2 [if used] and
installing jumper between Y1 and R.)

3. Set mixed air thermostat (MAT.) at lowest

setting. Outdoor air damper goes to fully open
position (indoor air damper closes).

4. Set mixed air thermostat at highest setting. Out­

door air damper goes to fully closed position
(indoor air damper opens).

5. Adjust mechanical linkage for correct position­

ing if necessary. If cooling was simulated in 2,
remove jumper and reconnect thermostat wire(s).

DAMPER VENT POSITION SETTING

1. Set fan switch at ON (continuous fan operation)

and close niglit switch if used.

2. Set system selector switch at OFF.
3. Remove cap from vent adjustment screw on

damper motor terminal box cover.

4. Turn adjustment screw slowly until dampers

assume desired vent position. Do not manually
operate damper motor. Damper to motor will

result.

POWER FAILURE — Dampers do not have a
spring return. In event of power failure, dampers
remain in position until power is restored. Do not
manually operate damper motor.

Refrigerant Charge

— Amount of refrigerant charge

is listed on unit nameplate (also refer to Table 1).

Refer to Carrier Standard Service Techniques

Manual, Chapter 1, Refrigerants.

Unit panels must be in place when unit is

operating during charging procedure.
NO CHARGE — Use standard evacuating tech­
niques. After evacuating system, weigh in the
specified amount of refrigerant. (Refer to Table 1.)

LOW CHARGE COOLING — Using appropriate

cooling charging chart. Fig. 19, 20 or 21 add refrig­
erant until conditions of the chart are met. Note
that charging charts are different from ones nor­
mally used. Charts are based on charging units to