Fig. 8 — timer sequence chart – Carrier 38AE User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Head Pressure Control

by means of/an

cycling is a

standard feature of 38AE012-016 units. The no. 2 fan cy­
cles in response to changes in liquid pressure. The switch

cycles the fan off at 126 ± 4 psig (869 ± 28 kPa) as pres­
sure decreases, and cycles back on at 257 (-1-5, -0) psig

(1772 [-f 103, -0] kPa).

CONTROL

SET POINT
ADJUSTMENT

NUT

PRESSURE

DIFFERENTIAL

ADJUSTMENT

SCREW

VALVE BODY

BYRASS

PISTON

DIFFERENTIAL SCREW'

SEALING CAP

(CAP MUST BE REPLACED

TO PREVENT REFRIGERANT LEAKAGE)

Fig. 7 — Compressor Capacity Controi Unloader

Time Guard® II Circuit

provides for a delay of ap­

proximately 5 minutes before restarting compressor after shut­
down from safety device action.

On start-up, the Time Guard II timer causes a delay of

approximately 3 seconds after thermostat closes.

On compressor shutdown, the timer recycles for approx­

imately 5 minutes. During this time, the compressor cannot
restart.

Refer to Fig. 8 and to label diagram on unit.

TIME DELAY TIMING SEQUENCE

T1-T2

---------- RUNNING TIME---------- »■

p«------ 3SEC ------------------------- »■

5 MIN

wimmmmmmimiri.

WIA

DENOTES CLC6ED CONTACTS

Fig. 8 — Timer Sequence Chart

Winter-Start Control (If Required)

- install Ac­

cessory Package 38AE900021.

Crankcase Heater

prevents refrigerant migration and

compressor oil dilution during shutdown whenever com­
pressor is not operating. It is wired into the control circuit,

cycling with the compressor, off when compressor is run­
ning, and on when compressor cycles off.

Both compressor service valves must be closed when­

ever crankcase heater is deenergized for more than 6 hours.
The crankcase heater is operable as long as the control cir­
cuit is energized.

Outdoor Fans

— Each fan is supported by a formed-

wire mount bolted to the fan deck and covered with a wire
guard. The exposed end of the motor shaft is covered with
a rubber boot. In case a fan motor must be repaired or re­

placed, be sure the rubber boot is put back on when the fan
is reinstalled and be sure the fan guard is in place before

starting the unit. Figure 9 shows the proper position of the
mounted fan. Fan motors have permanently lubricated
bearings.

Lubrication

FAN MOTORS have sealed lubrication bearings. No pro­
visions for lubrication are made.

COMPRESSOR has its own oil supply. Loss of oil due to a
leak in the system should be the only reason for adding oil
after the system has been in operation. See Oil Charge

section.

Advertising