Carrier 38AK007 User Manual

Installation, start-up and service instructions, A warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

38AK007

Air-Cooled Condensing Unit

Installation, Start-Up and Service

Instructions

SAFETY COIMSIDERATIONS

Installing and servicing air-conditioning equipment can

be hazardous due to system pressure and electrical compo­
nents. Only trained and qualified service personnel should

install or service air-conditioning equipment.

When working on air-conditioning equipment, observe

precautions in literature and on tags and labels attached to
unit.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Read these instructions

thor­

oughly. Consult local building codes and National Electri­
cal Code (NEC) for special installation requirements.

A WARNING

Before installing or servicing system, always turn off
main power to system. There may be more than one
disconnect switch. Electrical shock can cause personal
injury.

INSTALLATION

Step 1 — Complete Pre-Installation Checks

UNCRATE UNIT — Remove unit packaging except for
the top skid assembly and wood bumpers, which should be
left in place until after unit is rigged into place.

INSPECT SHIPMENT — File claim with shipping com­
pany if shipment is damaged or incomplete.

CONSIDER SYSTEM REQUIREMENTS

• Consult local building codes and NEC for special instal­

lation requirements.

Allow sufficient space for airflow clearance, wiring,

refrigerant piping, and servicing unit. See Eig. 1 and
Table 1.

• Locate unit so that condenser airflow is unrestricted on

all sides and above. Refer to Fig. 1.

• Unit may be mounted on a level pad directly on base

rails or mounted on raised pads at support points. See
Table 2 for weight distribution based on recommended
support points.

NOTE: If vibration isolators are required for a particular in­
stallation, use data in Table 2 to make proper selection.

Table 1 — Physical Data

UNIT 38AK

007

OPER WEIGHT (lb)

340

REFRIGERANT*

22

COMPRESSOR

on (oz)

65

CONDENSER AIR FAN

Number...Rpm 60 Hz

50 Hz

Diameter (in.)
Motor Hp (NEMA)

Nominal Cfm Total

Propeller; Direct Drive

1.. .850
1.. 708

26

Vs

3800

CONDENSER COIL

Face Area (sq ft)
Storage Capacity (lb)t

12 24
11.264

CONNECTIONS (sweat)

Suction (in.)
Liquid (In.)

1V8

V

2

CONTROLS

Pressurestat Settings

High Cutout

Cut-in

Low Cutout

Cut-in

426 ± 7 psig

320 ± 20 psig

7 ± 3 psig

22 ± 5 psig

FUSIBLE PLUG

200 F

‘Unit is factory supplied with holding charge only.
fStorage capacity of condenser coil with coil 80% full of liquid R-22

at 124 F

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book|1 |4

PC 111

Catalog No 633-809

Printed in U.S A

Form 38AK-2SI

Pg 1

6-92

Replaces: New

Tab 3a 2a