Lubrication, Condenser-fan adjustment (fig. lo) – Carrier 38AK007 User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOP VIEW

4. Remove device holding coil sections together at return

end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See
Fig. 9.

5. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and de­
bris. Clean the outer surfaces with a stiff brush in the

normal manner.

6. Reposition the outer coil section, and remove the coil

comer post from between the top panel and side panel.
Secure the sections together. Install the coil comer post
and replace all screws.

Lubrication

COMPRESSORS — Each compressor is charged with cor­

rect amount of oil at the factory.

FAN MOTOR BEARINGS — Fan motor bearings are of
the permanently lubricated type. No further lubrication is
required.

Condenser-Fan Adjustment

(Fig. lO)

1. Shut off unit power supply.

2. Remove condenser-fan assembly (grille, motor, motor

cover, and fan).

3. Loosen fan hub setscrews.

4. Adjust fan height as shown in Fig. 10.

5. Tighten setscrews.

6. Replace condenser-fan assembly.

MOTOR COVER

OUTLET GRILLE

Fig. 10 — Condenser-Fan Adjustment

Advertising