Fig. 3 — power wiring connections – Carrier 38AK007 User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

FIELD POWER SUPPLY - All units except 208/230-v
units are factory wired for the voltage shown on the name­
plate. If the 208/230-v unit is to be connected to a 208-v

power supply, the transformer

must be rewired by moving

the black wire from the 230-v orange wire on the trans­
former and connecting it to the 200-v red wire from the

transformer. The end of the orange wire must then be
insulated.

Refer to unit label diagram for additional information.

Pigtails are provided for field wire connections. Use
factory-supplied splices or UL (Underwriters’ Laborato­
ries) approved copper/aluminum connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local

requirements.

Install field wiring as follows;

1. Install conduit through side panel openings.

2. Install power lines to connections as shown in Fig. 3.

Wrap connections with electrical tape.

Voltage to compressor terminals during operation must

be within voltage range indicated on unit nameplate (also
see Table 4). On 3-phase units, voltages between phases
must be balanced within

2% and the current within 10%.

Use the formula shown in Table 4, Note 2, to determine the

% voltage imbalance. Operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation would in­
validate any applicable Carrier warranty.

LEGEND

C

— Contactor

NEC

— National Electrical Code

---------- Field Wiring

Factory Wiring
Splice Connection
(Factory Supplied)

Fig. 3 — Power Wiring Connections

Table 4 — Electrical Data

UNIT

NOMINAL VOLTAGE

VOLTAGE RANGE

COMPR

OFM

POWER SUPPLY

(V-Ph-Hz)

MIN

MAX

RLA

LRA

FLA

MCA

MOCP

208/230-3-60

187

254

19.0

142

1.9

25 6

351

460-3-60

414

508

9.5

72

1 0

12.9

17.6

38AK007

575-3-60

518

632

76

58

1.9

11.4

15.2

220-3-50

198

242

19.0

142

1.9

25.6

35.1

400-3-50

360

440

9.5

72

1.0

129

17.6

LEGEND

Canadian Standards Association
Full Load Amps
Heating, Air Conditioning and Refrigeration

Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps

CSA
FLA
HACR
LRA
MCA
MOCP

NEC
OFM
RLA

NOTES:
1 In compliance with NEC requirements for multimotor and combi­

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt­
age is greater than 2%.
Use the following formula to determine
the % voltage imbalance.

max voltage deviation from average voltage

= 100

X --------------------------------------------------------- -----------------------------------

average voltage

Example: Supply voltage is 460-3-60.

AB = 452

V

BC = 464

V

AC = 455

V

Average Voltage =

452 -H 464 -H 455

1371

3

^ 457

NOTE: The 575-v units are CSA only.

(AB) 457 - 452 = 5

V

(BC) 464 - 457 = 7

V

(AC) 457 - 455 = 2

V

Maximum deviation is 7 v.

Determine % voltage imbalance

7

% Voltage Imbalance = 100 x — = 1 53%

457

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more

than 2%, contact your local electric utility company immedi­
ately.

Advertising