Performance data, Standard ratings* — refrigerant 22, Minimum capacity step (%) – Carrier 30GB060 User Manual

Page 7: 1 1 i zero load at 0°f (-17.8 c) opt, 3 i zero load at 40 f (4.4 c) opt, I 2 i zero load at 20 f (-6.5 c) opt, Performance data -9

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Performance data

STANDARD RATINGS* — REFRIGERANT 22

UNIT

CAPACITY

COMPRESSOR

POWER INPUT

(kW)

FAN POWER

COOLER WATER

PRESSURE DROP

(ft water)

ENERGY EFFICIENCY

RATIO

(EER)

30GB

(tons)

(Btuh)

(kW)

060

59 7

716,400

68.4

7.81

13.7

94

*Per ARl Standard 590-81, Section 7 2

NOTE: 95 F condenser entering air temperature; 54 F entering/
44 F leaving cooler water; 0 0005 № • hr • °F/Btu cooler fouling

allowance.

EER

Capacity

(Btuh)

Input Power (W)

30GB060 PART-LOAD EFFICIENCY (EXV UNITS ONLY)

BUILDING COOLING LOAD PROFILE

MINIMUM CAPACITY STEP (%)

STANDARD UNIT

MODEL 30GB

STANDARD UNIT‘

WITH ACCESSORY

UNLOADERt

060

29

29

‘Includes factory-furnished unloader where applicable.

fWith field-installed accessory unloader

NOTE: See Table of Capacity Control Steps.

(17.8) (12 1) (-6.5) (-1) (4.5) (10) (15.5) (21) (265)02.9) (37.9) (C)

OUTDOOR TEMPERATURE

1

1

I

ZERO LOAD AT 0°F (-17.8 C) OPT

3

I

ZERO LOAD AT 40 F (4.4 C) OPT

% SYSTEM

FULL LOAD

OUTSIDE

AMBIENT

TEMP

UNIT

EER

% SYSTEM

FULL LOAD

OUTSIDE

AMBIENT

TEMP

UNIT

EER

F

C

F

C

100

95.0

35.0

9.4

100

95 0

35.0

94

90

85 5

29.8

10.6

90

89 5

31.9

103

80

76 0

24.3

11.8

80

84 0

28.9

11

1

70

66

5

19.0

13.0

70

78 5

25.8

12.0

60

57.0

13.9

14.2

60

73 0

22

8

12

8

50

47.5

8.5

16.9

50

67.5

19 7

142

40

38.0

3 1

21.6

40

62.0

16 7

17.3

30

28 5

-

2.0

26.2

30

56.5

136

20.4

I 2 I ZERO LOAD AT 20 F (-6.5 C) OPT

I 4 I ZERO LOAD AT 55 F (12.5 C) OPT

% SYSTEM

FULL LOAD

OUTSIDE

AMBIENT

TEMP

UNIT

EER

% SYSTEM

FULL LOAD

OUTSIDE

AMBIENT

TEMP

UNIT

EER

F

C

F

C

100

95 0

35.0

9.4

100

95.0

35.0

9.4

90

87 5

30.9

10.0

90

91 0

32

8

9.8

80

80.0

26 5

10.5

80

87.0

30.6

10.2

70

72.5

22.3

11.1

70

83 0

28.3

10.6

60

65.0

18

2

11

6

60

79.0

26.1

10.9

50

57.5

14.0

12.6

50

75 0

23.9

11

2

40

50.0

10.0

14.7

40

71 0

21 7

12.7

30

42.5

5.9

16.9

30

67.0

19.3

14.4

ODT

— Outdoor Temperature

NOTES:
1

Above efficiency ratings obtained at 54/44 F (12.2/6.7 C) cooler

water; full load at 95 F (35 0).

2

The longer the time operating at low temperatures, the greater the

difference in operating costs favoring a Flotronic™ unit over a
standard TXV unit

Contact your local Carrier representative for a computer analysis
of operating costs.

EER = Energy Efficiency Ratio

Capacity (Btuh)

Input Power (W)

Advertising