Guide specifications

1. GENERAL

1.1 Furnish and install complete, factory-assembled

air-cooled reciprocating liquid chiller units of the

type, size and capacity shown on the equipment

schedules. Unit shall be for outdoor use and rated

in accordance with ARI Standard 590 latest edition.

1.2 Equipment schedules and specifications are based

on Carrier Model 30GB060.

1.3 Reciprocating liquid chillers specified in this section

are of the air-cooled single-piece unit packaged type.

1.4 Units shall be of the packaged air-cooled type as

shown on the drawings and consist of a reciprocating

compressor or multiples thereof, direct-expansion

liquid cooler, air-cooled condenser and factory

wiring and piping contained within the unit en­

closure. Unit shall contain a complete operating

charge of refrigerant R-22.

1.5 Unit shall contain factory-installed diagnostic

system, capable of indicating status of all safeties

and energizing remote alarm.

1.6 Unit construction shall comply with ANSI B9.1

safety code, NEC (National Electrical Code) and

ASME Code.

1.7 Unit shall be capable of starting with up to 95 F

(35C) entering water temperature to the cooler.

1.8 Unit shall control leaving water temperature

±_____ ^F (____ ^C) from design point.

1.9 Unit shall be listed with UL.

2. UNIT CASING

2.1 Unit shall be enclosed in a galvanized steel casing,

zinc phosphatized, and coated with a baked enamel

finish, capable of withstanding Federal Test Method

Standard No. 141 (Method 6061) 500-hour salt

spray test.

3. COMPRESSOR

3.1 Each compressor shall be of the reciprocating

serviceable hermetic type only, and shall be

equipped with an automatically reversible oil pump,

operating oil charge, suction and discharge shutoff

valves, and shall be factory mounted on spring

vibration isolators.

3.2 Compressor motor shall be cooled by suction gas

passing around motor winding and shall be thermally

protected. Manual restart shall be required after

stoppage due to thermal and pressure overload.

3.3 Each compressor shall be equipped with an insert

type crankcase heater factory sized to control oil

dilution during shutdown.

3.4 Compressor speed shall not exceed 1750 rpm

(29.2 rps).

4. COOLER

4.1 Cooler shall be shell-and-tube type, with removable

heads. Seamless copper tubes shall be rolled into

tube sheets.

4.2 Cooler shall be tested and stamped in accordance

with ASME code for refrigerant side working

pressure of 235psig (1620 kPa) and a minimum

water side working pressure of 150 psig (1034 kPa).

4.3 Shell shall be insulated with a minimum of 3/4-in.

(19-mm) closed cell polyvinyl chloride (PVC) foam

insulation of maximum K factor 0.28. Heaters along

the shell, under the insulation, shall protect cooler

against freeze-up down to 10 F (-12 C).

4.4 Cooler shall have 2 independent direct-expansion

refrigerant circuits for all models.

5. CONDENSER

5.1 Air-cooled condenser coils shall have aluminum

(copper) fins mechanically bonded to seamless

copper tubes, cleaned, dehydrated, sealed, leak

tested at 150 psig (1034 kPa) and pressure tested

at 450 psig (3103 kPa).

5.2 Condenser fans shall be propeller type with PVC-

coated steel wire safety guards, balanced statically

and dynamically and discharge vertically.

5.3 Condenser fan motors shall have inherent over­

current protection.

6. REFRIGERANT COMPONENTS

6.1 Refrigerant circuit components shall include hot-gas

muffler, high side pressure relief device, liquid-line

shutoff valve, replaceable-core filter drier, moisture

indicating sight glass, and stepper motor actuated

electronic expansion valve (or thermal expansion

valve).

6.2 Expansion valves shall have maximum operating

pressure characteristics to limit inlet suction

pressure.

6.3 If unloaders are to be used, they shall be electrically

actuated suction cutoff cylinder unloaders.

6.4 For 30GB060 units, gages are available as

accessories.

7. CHILLER CONTROLS

7.1 Unit controls, including microprocessor, shall be

factory mounted and wired in a weatherproof

enclosure with hinged access doors for easy access.

Unit shall have automatic lead-lag available with

accessory unloader package. All units shall have

pumpdown at beginning and end of every circuit

cooling cycle, loss-of-charge protection, inherent

low water flow protection, low chilled water tem­

perature safety, low- and high-suction superheat

protection for each circuit. Low oil pressure

protection for each circuit, individual solid-state

compressor protection board and ground current

protection for each compressor are accessories

for 30GB060. Unit shall have low control voltage

to unit, field power and control circuit terminal

blocks, compressor and fan motor circuit breakers,

control circuit breaker, ON/OFF switch, replace­

able relay board, leaving chilled water set point

board, and a diagnostic digital display module, a

microprocessor board, a temperature reset board

(accessory).

7.2 Unit shall control capacity based upon leaving

water temperature and will be compensated by

return water temperature.

7.3 Capaciti! control — Chillers shall have no less

than 4 steps of control.

15