Cooling capacities - 30gb060, Performance data (cont), Legend – Carrier 30GB060 User Manual

Page 9

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Performance data (cont)

COOLING CAPACITIES - 30GB060

CONDENSER ENTERING AIR TEMPERATURE (F)

LCWT

85

90

95

Cap.

SDT

kW

Cooler

Cap.

SDT

kW

Cooler

Cap.

SDT

kW

Cooler

Flow

Rate

PD

Flow

Rate

PD

Flow

Rate

PD

40

58.5

113.2

63.7

139 9

124

56 7

1177

65.4

135.6

11 7

55 0

122.1

67.0

131 5

11.0

42

60 9

114.3

65.1

145.7

13.4

59.1

118.7

66.9

141.4

12.6

57.3

123 2

68.6

137.1

11.9

44

63 4

115.3

66.5

151.7

144

61.5

119.8

68.4

147.2

13.6

59.7

124.2

70.1

142 9

129

45

64.6

115.9

67.2

154.7

15 0

62 7

120 3

69.1

150.2

14.2

60.9

124

8

70.9

145

8

13 4

46

65.9

116.5

67.9

157.8

15

6

64.0

120 9

69 9

153 2

14.7

62.1

125.3

71 7

148.7

13.9

48

68.4

1176

69.4

164 0

16.8

66.5

122.0

71.4

159 4

15.9

64

6

126.5

73.3

154

8

15.0

50

71.1

118.8

70.8

170.4

18.0

69 1

123.2

72 9

165.7

17 1

67.1

127

6

74.9

161.0

16

2

55

77.9

121.8

74

6

187.0

21.5

75.8

126

2

76 9

182.0

20 5

73.8

130.6

79.1

177 0

19.4

60

85.2

125.1

78.5

204

6

25.6

82 9

129.4

81.0

199 3

24.3

80.7

133

8

83 4

193.9

23.1

CONDENSER ENTERING AIR TEMPERATURE (F)

LCWT

105

115

Cooler

Cooler

Cap.

SDT

kW

Flow
Rate

PD

Cap.

SDT

kW

Flow

Rate

PD

40

51.6

131.1

70.0

123 3

9.7

48.1

140.0

72

6

114.9

8.5

42

53.8

132.1

71.7

128 7

10.5

50 2

141.0

74 4

120.1

92

44

56.1

133 2

73 4

134 2

11 4

52.4

142.0

76.3

125 4

10

0

45

57.2

133.7

74.3

137.0

11 9

53 5

142.5

77.3

128

1

10.5

46

58.4

134 2

75.1

139.9

124

54

6

143.1

78.2

130

8

10.9

48

60.8

135.3

76 9

145.7

13.4

56 9

144.1

80.1

136.3

11

8

50

63 2

136.4

78.7

151

6

144

59 2

145.2

82.1

142.0

12.7

55

69 5

139.3

83.2

166

8

17.3

60

76.2

142.4

87.8

183.1

20.7

Cap.
Flow Rate

kW
LCWT
PD
SDT

NOTES:

1

2

LEGEND

Cooling Capacity Tons of Refrigeration
U S Gpm
Compressor Power input
Leaving Chilied Water Temperature (F)
Pressure Drop (Ft of Water)
Compressor Saturated Discharge Temperature (F)

Ratings appiy to units with electronic or thermai expansion vaives.

Aii ratings are based on.
a. A cooler chilled water temperature rise of 10° F. When greater

accuracy is desired, correct design LCWT, before entering
rating tabies, by reference to the LCWT correction curve.

b. A fouling factor of 0.0005 in the cooler,
c Refrigerant 22.

3

When a corrected LCWT is used, cooler pressure drop must also

be corrected for new LCWT :

a Enter rating tabie for corrected LCWT By interpolation,

determine corrected capacity (tons) and power input (kW) to
compressor at its rated voltage,

b Calculate corrected flow rate through the cooler.

24

X

capacity in tons

X

X

. — “ U S Qpm

temperature rise F

c.

Enter cooier pressure drop curve at corrected fiow rate and

read pressure drop

4. When chiiled water temperature rise is iess than 5°F, high fiow

rate will normally be accompanied by an excessive pressure drop.
In such cases, contact your Carrier representative for speciai

selection of a cooler with wider baffle spacing.

5

lO

i5

20

COOLER CHILLED WATER TEMPERATURE RISE (F)

Above 10F, ADD correction to design LCWT, below 10 F, SUBTRACT