INFINITY CONTROLLED LOW AMBIENT COOLING

NOTE:

When this unit is operating below 33°F (13°C) outdoor

temperature, provisions must be made for low ambient operation.
This unit is capable of low ambient cooling down to 0°F
(-18°C).ONLY when using the Infinity control. A low ambient kit
is not required, and the outdoor fan motor does not need to be
replaced for Infinity controlled low ambient operation.

Low

ambient cooling must be enabled in the UI set-up.

Fan may not

begin to cycle until about 40°F (4°C).OAT, Fan will cycle based
on coil and outdoor air temperature. Infinity controlled low

ambient mode operates as follows:

• In high stage, fan is off when outdoor coil temp is <outdoor air

temperature plus 3°F(f.7°C) or outdoor fan has been ON for 30

minutes, (Fan is turned off to allow refrigerant system to

stabilize.)

• In low stage, fan is off when outdoor coil temp is <outdoor air

temperature plus f°F (,6°C) or outdoor fan has been ON for 30

minutes, (Fan is turned off to allow refrigerant system to

stabilize.)

• In high stage and low stage, fan is on when outdoor coil temp >

outdoor air temperature plus 23°F (f3,8°C) or outdoor coil temp

> 80°F (27 °C) or if outdoor fan has been OFF for 30 minutes,

(Fan is turned on to allow refrigerant system to stabilize.)

• Low-pressure switch is ignored for first 3 minutes during low

ambient start up. After 3 minutes, if LPS trips, then outdoor fan

motor is turned off for f 0 minutes with the compressor running. If

LPS closes within fO minutes then cooling continues with the

outdoor fan cycling per the coil temperature routine listed above

for the remainder of the cooling cycle. If the LPS does not close

within 10 minutes, then the normal LPS trip response (shut down

cooling operation and generate LPS trip error) will occur.

DEHUMIDIFICATION MODE

This Infinity system can be used to dehumidify the living space.
See UI Installation Instructions for more details,

SEOUENCE OF OPERATION-GAS HEAT

NOTE: Infinity control must be grounded for proper operation or
control will lock out,

NOTE:

If a power interruption occurs during a call for heat, the

control will start a 90-second blower only ON period two seconds
after power is restored, if the UI is still calling for gas heating. The
amber LED light will flash code 12 during the 90-second period,
after which the LED will be ON continuously, as long as no faults
are detected. After the 90-second period, the unit will respond to
the UI normally,

GAS HEAT MODE AND ADJUSTMENTS

When the UI calls for gas heat, the Infinity furnace board performs
a self-check, verifies the pressure switch is open, and starts the
inducer on high speed,

1, Inducer Pre-purge Period: When the inducer motor comes

up on high speed, the pressure switch closes, and the
Infinity ignition control on the furnace board begins a 13
second pre-purge period. If the pressure switch fails to
remain closed, the inducer will remain running. After the
pressure switch re-closes, the Infinity ignition control will
begin a 13 second pre-purge period.

2, Trial-For-Ignition Sequence: The spark igniter will spark

for 3 seconds. The main gas valve relay contact closes to
energize the gas valve on low stage. After 3 seconds, the
igniter is de-energized and a 2-second flame-proving

period begins. NOTE:

The unit always lights on high

speed inducer and low stage gas valve operation,

3, Flame-Proving: When the burner flame is proved at the

flame-proving sensor, the furnace control determines what
heating stage to run based on feedback from the UI. If the
UI is asking for low stage gas heat, the ignition control will
change the inducer speed to low speed and keep the gas
valve energized on low stage. If the UI is asking for high
stage gas heat, the ignition control will maintain running the
inducer on high speed and energize the gas valve’s high
stage relay to increase gas flow.

If the burner flame is not proved within 2 seconds, the control will
close the gas valve and repeat the ignition sequence up to 3 more
Trials-For-Ignition before going to Ignition-Lockout. Lockout
will reset automatically after 3 hours, by momentarily interrupting
230 VAC power, or by interrupting 24 VAC power at SECl or
SEC2 to the furnace board.

If flame is proved when there should be no flame present, control
will lock out of Gas-Heating mode and operate the inducer motor
until flame is no longer proved,

4, Blower-On Delay:

If the burner flame is proven,

approximately 37 seconds after the gas valve is opened the
Indoor Blower is turned on to the appropriate speed for the
gas heating stage.

Simultaneously, the humidifier terminal HUM and electronic air
cleaner terminal EAC-1 are energized throughout the heating
cycle,

NOTE:

EAC-2 terminal is common with L2 and will have

113VAC-to-ground when unit is powered.

3, Blower-Off Delay: When the call for gas heat is satisfied,

the gas valve is de-energized, stopping the flow of gas to
the burners, and de-energizing the HUM terminal. The
inducer motor will remain on for a 4-second post-purge
period. The indoor blower and air cleaner terminal EAC-1
will remain energized for 90, 120, 130, or 180 seconds
(depending on selection of blower-off delay selected in the
UI). The factory-set default is 120-second blower-OFF
delay.

CHECK GAS INPUT (NATURAL GAS)

A. CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in component
damage.

Do not

redrill an orifice. Improper drilling (burrs,

out-of-round holes, etc.) can cause excessive burner noise
and misdirection of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check
orifice hole with a numbered drill bit of correct size.

A. WARNING

EIRE HAZARD

Failure to follow this warning could result in personal
injury, death and/or property damage,

DO NOT bottom out gas valve regulator adjusting screws.
This can result in unregulated manifold pressure and result
in excess overfire and heat exchanger failures.